| Plan Review Notes For Permit 09020107 |
| Permit Number |
09020107 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-04-30 17:10:28 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- PROVIDE COMPLETE DETAILS/SPECS FOR STAIRWAY | | | HANDRAILS. SEC. R311.5.6. | | | 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS (DCA RULE | | | 9B-72) FOR: A) LOUVERED DOOR IN GENERATOR ROOM. B) NEW | | | FOLDING DOORS IN CABANA ROOM. C) PRECAST LINTELS (ONE | | | SUBMITTED IS MISSING THE DRAWINGS). D) GENERATOR | | | LOUVERS (INFORMATION SUBMITTED IS NOT THE APPROVED | | | PRODUCT APPROVAL FL 10088). E) FLAT ROOF (CIRCLE | | | SELECTED APPROVED ASSEMBLY AND RE-SUBMIT PACKAGE). | | | ***REMAINDER: DESIGNER OF RECORD TO REVIEW AND APPROVE | | | ALL PRODUCT APPROVALS. | | | 3- PROVIDE SIZES FOR CABANA ROOF SCUPPERS (SEC. R903.4) | | | AND OVERFLOW SCUPPERS TO COMPLY WITH SEC. R903.4.1. | | | 4- RE-SUBMIT SOIL TEST REPORT WITH ENGINEER'S ORIGINAL | | | SIGNATURE (NOT COLOR COPY) AND PROVIDE ENGINEERING FIRM | | | CERTIFICATE OF AUTHORIZATION NUMBER (SEC. | | | 61G15-23.001). | | | 5- DESIGNER OF RECORD TO REVIEW AND APPROVE REVISED | | | PRODUCT APPROVAL FOR ROLL UP SHUTTERS AND RE-SUBMIT | | | PACKAGE. | | | 6- RE-SUBMIT SITE SPECIFIC ENGINEERING FOR BALCONY | | | GUARDRAIL SYSTEM. SEE COMMENTS ON PACKAGE SUBMITTED. | | | 7- ENERGY CALCULATIONS ARE TAKING THE WHITE ROOF | | | CREDIT. PROVIDE WHITE ROOF TEST RESULTS AS REQUIRED BY | | | SEC. 13-607.1.A.5 FBC 2004. |
|