2009-04-30 17:10:28BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE COMPLETE DETAILS/SPECS FOR STAIRWAY
 HANDRAILS. SEC. R311.5.6.
 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS (DCA RULE
 9B-72) FOR: A) LOUVERED DOOR IN GENERATOR ROOM. B) NEW
 FOLDING DOORS IN CABANA ROOM. C) PRECAST LINTELS (ONE
 SUBMITTED IS MISSING THE DRAWINGS). D) GENERATOR
 LOUVERS (INFORMATION SUBMITTED IS NOT THE APPROVED
 PRODUCT APPROVAL FL 10088). E) FLAT ROOF (CIRCLE
 SELECTED APPROVED ASSEMBLY AND RE-SUBMIT PACKAGE).
 ***REMAINDER: DESIGNER OF RECORD TO REVIEW AND APPROVE
 ALL PRODUCT APPROVALS.
 3- PROVIDE SIZES FOR CABANA ROOF SCUPPERS (SEC. R903.4)
 AND OVERFLOW SCUPPERS TO COMPLY WITH SEC. R903.4.1.
 4- RE-SUBMIT SOIL TEST REPORT WITH ENGINEER'S ORIGINAL
 SIGNATURE (NOT COLOR COPY) AND PROVIDE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER (SEC.
 61G15-23.001).
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE REVISED
 PRODUCT APPROVAL FOR ROLL UP SHUTTERS AND RE-SUBMIT
 PACKAGE.
 6- RE-SUBMIT SITE SPECIFIC ENGINEERING FOR BALCONY
 GUARDRAIL SYSTEM. SEE COMMENTS ON PACKAGE SUBMITTED.
 7- ENERGY CALCULATIONS ARE TAKING THE WHITE ROOF
 CREDIT. PROVIDE WHITE ROOF TEST RESULTS AS REQUIRED BY
 SEC. 13-607.1.A.5 FBC 2004.