 APPLICATION #09020107 ELECTRICAL PLAN REVIEW
 3600 N. FLAGLER DRIVE 2/25/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 COMMENTS FROM SHEET E200 RISER DIAGRAM.
  
 1} THE MANUFACTURERS SPECIFICATIONS SUBMITTED FOR THE
 GENERATOR ARE FOR A 70 KW GENERAC, NOTE #10, SHEET E200
 REFERENCES A KOHLER MODEL 60RZG. CORRELATE THESE AND
 SUBMIT SPECIFICATIONS FOR THE INTENDED INSTALLATION.
  
 2} THE GROUNDING ELECTRODE CONDUCTOR (NOTE #3 ON THE
 PLAN) MUST BE SIZED PER 250.66, SEE NOTE #1 FOR
 PARALLEL CONDUCTORS "1. WHERE MULTIPLE SETS OF
 SERVICE-ENTRANCE CONDUCTORS ARE USED AS PERMITTED IN
 230.40, EXCEPTION NO. 2, THE EQUIVALENT SIZE OF THE
 LARGEST SERVICE-ENTRANCE CONDUCTOR SHALL BE DETERMINED
 BY THE LARGEST SUM OF THE AREAS OF THE CORRESPONDING
 CONDUCTORS OF EACH SET".
  
 3} THE EQUIPMENT GROUND RAN TO ATS FROM PANEL ECB (NOTE
 #5 ON THE PLAN) MUST COMPLY WITH 250.122 (F)(1)- (F)
 CONDUCTORS IN PARALLEL WHERE CONDUCTORS ARE RUN IN
 PARALLEL IN MULTIPLE RACEWAYS OR CABLES AS PERMITTED IN
 310.4, THE EQUIPMENT GROUNDING CONDUCTORS, WHERE USED,
 SHALL BE RUN IN PARALLEL IN EACH RACEWAY OR CABLE. ONE
 OF THE METHODS IN 250.122(F)(1) OR (F)(2) SHALL BE USED
 TO ENSURE THE EQUIPMENT GROUNDING CONDUCTORS ARE
 PROTECTED.
 (1) BASED ON RATING OF OVERCURRENT PROTECTIVE DEVICE
 EACH PARALLEL EQUIPMENT GROUNDING CONDUCTOR SHALL BE
 SIZED ON THE BASIS OF THE AMPERE RATING OF THE
 OVERCURRENT DEVICE PROTECTING THE CIRCUIT CONDUCTORS IN
 THE RACEWAY OR CABLE IN ACCORDANCE WITH TABLE 250.122.
  
 4} NOTE #6 ON THE PLAN INDICATES #4/0 CONDUCTORS FROM
 THE GENERATOR TO THE ATS, INDICATE THE OVERCURRENT
 PROTECTION RATING OF THE GENERATOR BREAKER, SEE
 310.15(B)(6).
  
 5} REGARDING THE FEED TO PANEL "DP" FROM THE ATS, SEE
 COMMENT #3, EQUIPMENT GROUND SIZING PER 250.122.
 THESE COMMENTS ARE IN REFERENCE TO THE SERVICE LOAD
 CALCULATION
  
 6} THE GENERAL LIGHTING LOAD APPEARS TO BE INCORRECT AT
 4773 WATTS. THE SQUARE FOOTAGE FOR THE CALCULATION MUST
 COMPLY WITH 220.12-A UNIT LOAD OF NOT LESS THAN THAT
 SPECIFIED IN TABLE 220.12 FOR OCCUPANCIES SPECIFIED
 THEREIN SHALL CONSTITUTE THE MINIMUM LIGHTING LOAD. THE
 FLOOR AREA FOR EACH FLOOR SHALL BE CALCULATED FROM THE
 OUTSIDE DIMENSIONS OF THE BUILDING, DWELLING UNIT, OR
 OTHER AREA INVOLVED. FOR DWELLING UNITS, THE CALCULATED
 FLOOR AREA SHALL NOT INCLUDE OPEN PORCHES, GARAGES, OR
 UNUSED OR UNFINISHED SPACES NOT ADAPTABLE FOR FUTURE
 USE. THE LIGHTING LOAD IN THE CALCULATION DIFFERS FROM
 THE ONE ON PANEL SCHEDULE-DP.
  
 7} PER 210.11(C) (1) SMALL-APPLIANCE BRANCH CIRCUITS IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR
 ALL RECEPTACLE OUTLETS SPECIFIED BY 210.52(B). ONLY ONE
 IS CALCULATED.
  
 8} THE UNDER COUNTER REFRIGERATORS MARE CALCULATED AT
 600 WATTS BUT ARE LISTED AS 2000 WATTS TOTAL ON THE
 PANEL SCHEDULES. 220.14(A), 2005 NEC.
  
 9} THE AIR HANDLERS ARE MARKED #3&4 ON THE PANEL
 SCHEDULE BUT ARE MARKED #1&2 ON SHEET M200, CORRELATE
 SAME.
  
 10} THE VOLTAGE FOR THE A/C EQUIPMENT IS SHOWN AS 208
 ON SHEET M200. VERIFY WITH THE MANUFACTURER THAT THEY
 CAN OPERATE ON A 240 VOLT SYSTEM THAT IS THE OPERATING
 SYSTEM SHOWN IN THE LOAD CALCULATION
  
 11} THE PANEL LOCATION IN THE STORAGE ROOM IS IN
 VIOLATION OF 240.24(D) IF ANY IGNITABLE MATERIAL IS
 STORED IN THAT ROOM, INCLUDING POOL CHEMICALS, LAWN
 MOWERS (GAS), GASOLINE CONTAINERS ETC. THE PANEL SHOULD
 BE RELOCATED.
  
 12 A RECEPTACLE PER 210.63 IS REQUIRED FOR THE
 CONDENSING UNIT, WITHIN 25'
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER