| Date |
Text |
| 2009-02-24 11:15:10 | NEW RESIDENTIAL CONSTRUCTION (R3) , BUILDING REVIEW |
| | CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS. |
| | |
| | 1- PROPERTY IS LOCATED ON FLOOD ZONE A5. ELEVATION |
| | CERTIFICATE WILL BE REQUIRED PRIOR TO CERTIFICATE OF |
| | OCCUPANCY. THIS IS JUST A REMAINDER. |
| | |
| | 2- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FL. ST. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 3- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD |
| | (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING |
| | BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE |
| | DUE. |
| | |
| | 4- PROVIDE SPECIFICATIONS FOR FIRE RATED CEILING ABOVE |
| | GARAGE AS REQUIRED BY SEC. R309.2 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 5- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR |
| | HANDRAILS TO VERIFY COMPLIANCE WITH SEC. R311.5..6 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 6- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) LOUVERED DOORS, INCLUDING DOUBLE DOORS AS SHOWN ON |
| | GENERATOR ROOM AND ON CABANA BUILDING. |
| | |
| | B) WINDOW MULLIONS FOR CLERESTORY WINDOWS ON CABANA |
| | BUILDING. AND, CLEARLY MARK SPECIFIC MULLION SIZE AND |
| | ANCHORS TO BE USED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES. |
| | |
| | C) PRECAST LINTELS. |
| | |
| | D) FLAT ROOF PRODUCT APPROVAL FOR CABANA ROOF. |
| | NOTE: CHECK THE DESIGN PRESSURES FOR CORNER AND |
| | PERIMETER AREAS. CHECK GENERAL LIMITATIONS AND PROVIDE |
| | REQUIRED INFORMATION. |
| | |
| | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | 9- MINIMUM ROOF SLOPE FOR LOW SLOPE ROOF IS 1/4" PER |
| | FOOT AS REQUIRED BY SEC. R905.9 OR R905.11 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. REVISE 4" SLOPE SHOWN FOR |
| | CABANA FLAT ROOF. 4" DOESN'T PROVIDE THE 1/4" PER FOOT |
| | SLOPE. |
| | |
| | 10- PROVIDE DETAILS AND SPECIFICATIONS FOR ROOF |
| | DRAINAGE INCLUDING THE SCUPPERS AS REQUIRED BY SEC. |
| | R903.4 OF 2004 FLORIDA RESIDENTIAL CODE. SPECIFY |
| | LOCATION AND SIZES. |
| | |
| | 11- COORDINATE DESIGN PRESSURES SHOWN ON SHEET A400 |
| | WITH THE DESIGN PRESSURES SHOWN ON SHEET S100. |
| | |
| | 12- SPECIFY FIREBLOCKING MATERIAL AND LOCATION ON |
| | STAIRWAY AS REQUIRED BY SEC. R602.1.2 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 13- CLARIFY IF ALL WINDOWS ARE FIXED WINDOWS. AND, |
| | COORDINATE MANUFACTURER SPECIFIED ON WINDOW SCHEDULE |
| | AND PRODUCT APPROVAL SUBMITTED. THERE ARE TWO DIFFERENT |
| | MANUFACTURERS. MARVIN AND ULTIMATE. |
| | |
| | 14- THERE IS A BALANCE OF $15,239.36. |
| | |
| | 15- SPECIFY ATTIC SIZE AND LOCATION TO COMPLY WITH |
| | SECTION R807 OF 2004 FLORIDA RESIDENTIAL CODE. NOTE: |
| | MAKE SURE ENOUGH CLEARANCE IS PROVIDED FOR AIR HANDLER |
| | UNIT. ALSO, CLARIFY CEILING CONSTRUCTION ON MAIN HOUSE. |
| | IS IT VAULTED CEILING OR FLAT CEILING. BUILDING SECTION |
| | SHOWS VAULTED CEILING. |
| | |
| | 16- SHEET S100: |
| | A) SPECIFY FINISH FLOOR ELEVATION FOR LAUNDRY ROOM AND |
| | GENERATOR ROOM. REMEMBER THAT PROPERTY IS LOCATED ON |
| | FLOOD ZONE A5. |
| | |
| | B) REVISE MIN. DIMENSION FOR ZONE "A". MINIMUM |
| | DIMENSION IS 4'-0" AS REQUIRED BY FOOTNOTE A ON FIGURE |
| | R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 17- SHEET S103: |
| | A) SPECIFY FINISH FLOOR ELEVATION FOR ALL ROOMS. |
| | REMEMBER PROPERTY LOCATED ON FLOOD ZONE A5. |
| | |
| | B) REVISE MIN. DIMENSION FOR ZONE "A". MINIMUM |
| | DIMENSION IS 4'-0" AS REQUIRED BY FOOTNOTE A ON FIGURE |
| | R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 18- SHEET S200: REVISE FINISH FLOOR ELEVATION ON DETAIL |
| | 1/S200. COORDINATE WITH ITEM #17 ABOVE. |
| | |
| | 19- SHEET S301: REVISE SIZE OF STRUCTURAL BUCK ON |
| | TYPICAL DOOR BUCK DETAIL. NEED SIZE THAT PROVIDES FULL |
| | SUPPORT TO DOOR FRAME. SEE PRODUCT APPROVAL FOR SIZE OF |
| | JAMB AND REVISE AS REQUIRED. SEC. R613.6 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 20- CHECK SIZE OF GENERATOR AND SIZE OF GENERATOR ROOM. |
| | ACCORDING TO INFORMATION SUBMITTED, GENERATOR ROOM MAY |
| | NOT BE ADEQUATE FOR SIZE OF GENERATOR. CHECK IF IT |
| | MEETS THE VENTILATION AND ACCESS REQUIREMENTS. |
| | |
| | 21- GUARDRAIL ENGINEERING: |
| | A) ENGINEER TO PROVIDE ORIGINAL SEAL, SIGNATURE AND |
| | DATE IN ALL SHEETS AS REQUIRED BY SEC. 61G15-23.002 |
| | FLORIDA ADMINISTRATIVE CODE AND CHAPTER 471 FL. ST. |
| | |
| | B) SPECIFY FBC SPECIFIC EDITION (2007 WITH 2007 |
| | REVISIONS). |
| | |
| | C) CLEARLY IDENTIFY INFORMATION THAT APPLIES TO THIS |
| | SITE SPECIFIC PROJECT. EG: SPECIFIC GLASS THICKNESS, |
| | GUARDRAIL CAP SIZE, ANCHORS AND SPACING, ETC. ALSO, |
| | ENGINEER TO WRITE JOB ADDRESS FOR THIS SITE SPECIFIC |
| | PROJECT. |
| | |
| | 22- ROLL SHUTTERS PRODUCT APPROVAL: |
| | A) PROVIDE COMPLETE INFORMATION ON SHEET 21 OF 21. |
| | |
| | B) CLEARLY IDENTIFY WHICH MOUNTING CONDITIONS SHOWN ON |
| | SHUTTERS DRAWINGS APPLY TO THE PROPOSED INSTALLATION. |
| | SEE SHEET 2 OF 21. IF PROPOSED INSTALLATION IS NOT ON |
| | DRAWINGS, THEN SITE SPECIFIC ENGINEERING WILL BE |
| | REQUIRED.. SEE GENERAL NOTE #9 ON SHEET 1 OF 21. |
| | |
| | C) SPECIFY HOW MANY SPANS WILL BE REQUIRED FOR EACH |
| | OPENING. |
| | |
| | D) CHECK ANCHOR SPACING. COORDINATE WITH ITEM #22C |
| | ABOVE. |
| | |
| | 23- ENERGY CALCULATIONS: |
| | A) COORDINATE WALL TYPES WITH THOSE SHOWN ON FLOOR |
| | PLANS. THERE ARE NOT STEEL ADJACENT WALLS. SEE PLANS. |
| | |
| | B) CLARIFY WHAT TYPE OF CEILING IS "RBS' AS SPECIFIED |
| | ON ITEM #10. |
| | |
| | C) ENGINEER TO PROVIDE HIS NAME AND LICENSE NUMBER AS |
| | REQUIRED BY SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE |
| | CODE AND CHAPTER 471 FL. ST. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |