2009-02-24 11:15:10NEW RESIDENTIAL CONSTRUCTION (R3) , BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- PROPERTY IS LOCATED ON FLOOD ZONE A5. ELEVATION
 CERTIFICATE WILL BE REQUIRED PRIOR TO CERTIFICATE OF
 OCCUPANCY. THIS IS JUST A REMAINDER.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FL. ST.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 3- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.
  
 4- PROVIDE SPECIFICATIONS FOR FIRE RATED CEILING ABOVE
 GARAGE AS REQUIRED BY SEC. R309.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 5- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR
 HANDRAILS TO VERIFY COMPLIANCE WITH SEC. R311.5..6 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 6- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) LOUVERED DOORS, INCLUDING DOUBLE DOORS AS SHOWN ON
 GENERATOR ROOM AND ON CABANA BUILDING.
  
 B) WINDOW MULLIONS FOR CLERESTORY WINDOWS ON CABANA
 BUILDING. AND, CLEARLY MARK SPECIFIC MULLION SIZE AND
 ANCHORS TO BE USED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES.
  
 C) PRECAST LINTELS.
  
 D) FLAT ROOF PRODUCT APPROVAL FOR CABANA ROOF.
 NOTE: CHECK THE DESIGN PRESSURES FOR CORNER AND
 PERIMETER AREAS. CHECK GENERAL LIMITATIONS AND PROVIDE
 REQUIRED INFORMATION.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO
 FBC 2004.
  
 9- MINIMUM ROOF SLOPE FOR LOW SLOPE ROOF IS 1/4" PER
 FOOT AS REQUIRED BY SEC. R905.9 OR R905.11 OF 2004
 FLORIDA RESIDENTIAL CODE. REVISE 4" SLOPE SHOWN FOR
 CABANA FLAT ROOF. 4" DOESN'T PROVIDE THE 1/4" PER FOOT
 SLOPE.
  
 10- PROVIDE DETAILS AND SPECIFICATIONS FOR ROOF
 DRAINAGE INCLUDING THE SCUPPERS AS REQUIRED BY SEC.
 R903.4 OF 2004 FLORIDA RESIDENTIAL CODE. SPECIFY
 LOCATION AND SIZES.
  
 11- COORDINATE DESIGN PRESSURES SHOWN ON SHEET A400
 WITH THE DESIGN PRESSURES SHOWN ON SHEET S100.
  
 12- SPECIFY FIREBLOCKING MATERIAL AND LOCATION ON
 STAIRWAY AS REQUIRED BY SEC. R602.1.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 13- CLARIFY IF ALL WINDOWS ARE FIXED WINDOWS. AND,
 COORDINATE MANUFACTURER SPECIFIED ON WINDOW SCHEDULE
 AND PRODUCT APPROVAL SUBMITTED. THERE ARE TWO DIFFERENT
 MANUFACTURERS. MARVIN AND ULTIMATE.
  
 14- THERE IS A BALANCE OF $15,239.36.
  
 15- SPECIFY ATTIC SIZE AND LOCATION TO COMPLY WITH
 SECTION R807 OF 2004 FLORIDA RESIDENTIAL CODE. NOTE:
 MAKE SURE ENOUGH CLEARANCE IS PROVIDED FOR AIR HANDLER
 UNIT. ALSO, CLARIFY CEILING CONSTRUCTION ON MAIN HOUSE.
 IS IT VAULTED CEILING OR FLAT CEILING. BUILDING SECTION
 SHOWS VAULTED CEILING.
  
 16- SHEET S100:
 A) SPECIFY FINISH FLOOR ELEVATION FOR LAUNDRY ROOM AND
 GENERATOR ROOM. REMEMBER THAT PROPERTY IS LOCATED ON
 FLOOD ZONE A5.
  
 B) REVISE MIN. DIMENSION FOR ZONE "A". MINIMUM
 DIMENSION IS 4'-0" AS REQUIRED BY FOOTNOTE A ON FIGURE
 R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE.
  
 17- SHEET S103:
 A) SPECIFY FINISH FLOOR ELEVATION FOR ALL ROOMS.
 REMEMBER PROPERTY LOCATED ON FLOOD ZONE A5.
  
 B) REVISE MIN. DIMENSION FOR ZONE "A". MINIMUM
 DIMENSION IS 4'-0" AS REQUIRED BY FOOTNOTE A ON FIGURE
 R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE.
  
 18- SHEET S200: REVISE FINISH FLOOR ELEVATION ON DETAIL
 1/S200. COORDINATE WITH ITEM #17 ABOVE.
  
 19- SHEET S301: REVISE SIZE OF STRUCTURAL BUCK ON
 TYPICAL DOOR BUCK DETAIL. NEED SIZE THAT PROVIDES FULL
 SUPPORT TO DOOR FRAME. SEE PRODUCT APPROVAL FOR SIZE OF
 JAMB AND REVISE AS REQUIRED. SEC. R613.6 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 20- CHECK SIZE OF GENERATOR AND SIZE OF GENERATOR ROOM.
 ACCORDING TO INFORMATION SUBMITTED, GENERATOR ROOM MAY
 NOT BE ADEQUATE FOR SIZE OF GENERATOR. CHECK IF IT
 MEETS THE VENTILATION AND ACCESS REQUIREMENTS.
  
 21- GUARDRAIL ENGINEERING:
 A) ENGINEER TO PROVIDE ORIGINAL SEAL, SIGNATURE AND
 DATE IN ALL SHEETS AS REQUIRED BY SEC. 61G15-23.002
 FLORIDA ADMINISTRATIVE CODE AND CHAPTER 471 FL. ST.
  
 B) SPECIFY FBC SPECIFIC EDITION (2007 WITH 2007
 REVISIONS).
  
 C) CLEARLY IDENTIFY INFORMATION THAT APPLIES TO THIS
 SITE SPECIFIC PROJECT. EG: SPECIFIC GLASS THICKNESS,
 GUARDRAIL CAP SIZE, ANCHORS AND SPACING, ETC. ALSO,
 ENGINEER TO WRITE JOB ADDRESS FOR THIS SITE SPECIFIC
 PROJECT.
  
 22- ROLL SHUTTERS PRODUCT APPROVAL:
 A) PROVIDE COMPLETE INFORMATION ON SHEET 21 OF 21.
  
 B) CLEARLY IDENTIFY WHICH MOUNTING CONDITIONS SHOWN ON
 SHUTTERS DRAWINGS APPLY TO THE PROPOSED INSTALLATION.
 SEE SHEET 2 OF 21. IF PROPOSED INSTALLATION IS NOT ON
 DRAWINGS, THEN SITE SPECIFIC ENGINEERING WILL BE
 REQUIRED.. SEE GENERAL NOTE #9 ON SHEET 1 OF 21.
  
 C) SPECIFY HOW MANY SPANS WILL BE REQUIRED FOR EACH
 OPENING.
  
 D) CHECK ANCHOR SPACING. COORDINATE WITH ITEM #22C
 ABOVE.
  
 23- ENERGY CALCULATIONS:
 A) COORDINATE WALL TYPES WITH THOSE SHOWN ON FLOOR
 PLANS. THERE ARE NOT STEEL ADJACENT WALLS. SEE PLANS.
  
 B) CLARIFY WHAT TYPE OF CEILING IS "RBS' AS SPECIFIED
 ON ITEM #10.
  
 C) ENGINEER TO PROVIDE HIS NAME AND LICENSE NUMBER AS
 REQUIRED BY SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE
 CODE AND CHAPTER 471 FL. ST.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712