| Plan Review Notes For Permit 09020092 |
| Permit Number |
09020092 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-02-15 13:33:20 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. A SEPARATE INSTALLATION DETAIL FOR THE ROOFTOP | | | CONDENSER STAND WAS PROVIDED WITH THIS PERMIT | | | APPLICATION. THIS DETAIL DOES NOT CORRESPOND WITH THE | | | DETAIL PROVIDED ON MASTER PERMIT PLANS. WHICH IS TO BE | | | USED? PLEASE COORDINATE PLANS WITH SUBMITTAL | | | DOCUMENTATION. | | | | | | 2. PRE-ENGINEERED A/C STANDS ARE DEFINED AS STRUCTURAL | | | COMPONENTS PER FAC RULE 9B-72. PRODUCT APPROVAL IS | | | REQUIRED. THE SUBMITTAL DOES NOT INDICATE THIS PRODUCT | | | HAS BEEN APPROVED BY THE FLORIDA PRODUCT APPROVAL | | | SYSTEM. PROVIDE A COMPLETE FLORIDA PRODUCT APPROVAL | | | SUBMITTAL WHICH HAS BEEN APPROVED IN WRITING BY THE | | | MASTER PERMIT DESIGNER OF RECORD IN ACCORDANCE WITH | | | FBC-B 106.3.3. IF THE INTENT IS TO APPLY FOR A LOCAL | | | PRODUCT APPROVAL, PLEASE CONTACT A BUILDING PLANS | | | EXAMINER FOR ADDITIONAL INFORMATION REGARDING THIS | | | PROCESS. | | | | | | 3. WHEN RESUBMITTING, PLEASE BE SURE TO ADDRESS ALL | | | ZONING PLAN REVIEW COMMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|