Plan Review Notes
Plan Review Notes For Permit 09020088
Permit Number 09020088
Review Stop B
Sequence Number 1
Notes
Date Text
2009-02-18 14:15:41****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE EXPLAIN WHY ROOF ZONES 2 AND 3 HAVE THE SAME
 DESIGN PRESSURES FOR COMPONENTS AND CLADDING, FBC1609.
  
 2. PLEASE PROVIDE CALCULATIONS TO SHOW HOW YOU???VE
 DETERMINED DESIGN PRESSURE OF -39.9 FOR ROOF ZONES 2
 AND 3. TABLE F ON SHEET 7 THEN FURTHER REDUCES THE
 UPLIFT PRESSURES TO 30% DUE TO OPEN STRUCTURE,
 RESULTING IN A DESIGN PRESSURE OF 20.5. IS THIS FOR
 ROOF PRESSURES? IF NOT, WHAT DOES TABLE F APPLY TO?
  
 3. WHEN RESUBMITTING, FOR RECORD KEEPING PURPOSES
 PLEASE INDICATE ALL PERTINENT DETAILS IN INK RATHER
 THAN HIGHLIGHTER. YELLOW HIGHLIGHTER DOES NOT APPEAR
 WHEN SCANNED. FBC*106.
  
 4. 140MPH AND 20.5 HAVE BEEN MARKED ON TABLE F. TABLE D
 HAS 20PSF HIGHLIGHTED. PLEASE CLARIFY; HOW HAVE YOU
 DETERMINED 20PSF?
  
 5. SOME SHEETS SHOW A CONCRETE SLAB, OTHERS SHOW
 PAVERS. PLEASE CORRELATE.
  
 6. PLANS REFER TO FBC2004 WITH 2006 REVISIONS.
 GOVERNING CODE SHOULD INCLUDE 2007
 REVISIONS/SUPPLEMENTS; PLEASE REVISE.
  
 7. PROVIDE INFORMATION REGARDING THE ???CRESCENT.??? IT
 IS DEPICTED GRAPHICALLY, ALONG WITH THE ???CRESCENT
 HOLDER,??? BUT NO INFORMATION ABOUT EITHER WAS
 PROVIDED.
  
 8. PLEASE MARK ALL DETAILS PERTINENT TO THIS JOB.
  
 9. SEE FLOOR PLAN; SITE PLAN AND OTHER DETAILS SHOW
 THIS AS PARTIALLY FREESTANDING, BUT FLOOR PLAN SHOWS
 EXTERIOR WALLS ON TWO SIDES.
  
 10. FLOOR PLAN SHOWS SQUARE COLUMNS, STATES POST STYLE:
 SQUARE, SHEET 4 HAS ROUND COLUMN CONNECTION
 HIGHLIGHTED, SHEET 7 HAS ROUND COLUMN HIGHLIGHTED.
  
 11. FLOOR PLAN CONFLICTS WITH SHEET 2. FOUNDATION PLAN
 NOT CLEAR. PLANS SHOULD CLEARLY SHOW SCOPE OF WORK,
 FBC*106. IT APPEARS THAT SOME DETAILS ARE SPECIFIC TO
 THIS JOB, SOME ARE GENERIC ENGINEERING, BUT NOT ENOUGH
 DETAIL PROVIDED TO DETERMINE SCOPE AND ACTUAL PROPOSED
 CONSTRUCTION.
  
 12. SOME DETAILS SHOW MORE THAN ONE COLUMN, FLOOR PLAN
 SHOWS ONE.
  
 13. PLEASE EXPLAIN USE OF OPEN CLASSIFICATION,
 FBC1609.1.5.
  
 14. A COMPLETE REVIEW CANNOT BE DONE AT THIS TIME AS
 CONFLICTING INFORMATION WAS PROVIDED.
  