| Plan Review Notes For Permit 09020082 |
| Permit Number |
09020082 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-02-15 11:03:47 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PAGE M-1: NOTE #15 CALLS FOR NEW DUCT PENETRATION OF | | | SHAFT ENCLOSURE WITH FIRE DAMPER FOR OUTSIDE AIR. SHAFT | | | ENCLOSURES THAT ARE PERMITTED TO BE PENETRATED BY DUCTS | | | AND AIR TRANSFER OPENINGS SHALL BE PROTECTED WITH | | | APPROVED FIRE AND SMOKE DAMPERS INSTALLED IN ACCORDANCE | | | WITH THEIR LISTING PER FBCM 607.5.5.1. | | | | | | 2. PAGE M-1: IS THE CEILING SPACE ABOVE THE EXISTING | | | BATHROOMS ISOLATED FROM THE PLENUM CEILING ON THE REST | | | OF THE FLOOR? NOTE ON THIS PAGE INDICATES THE CEILING | | | SPACE THROUGHOUT IS A RETURN AIR PLENUM.THE DUCT ON THE | | | DISCHARGE SIDE OF PROPOSED NEW EF-1 WILL BE UNDER | | | POSITIVE PRESSURE AND CANNOT BE LOCATED IN A PLENU IN | | | ACCORDANCE WITH FBCM 601.3. | | | | | | 3. M AND P PAGES: MECHANICAL DETAIL CALLS FOR AUXILIARY | | | DRAIN PAN WITH A FLOAT SWITCH AND NO SECONDARY DRAIN | | | LINE WHILE PLUMBING PLAN SHOWS SECONDARY DRAIN LINE RUN | | | FROM THE AUXILIARY DRAIN PAN TO ABOVE A SINK. WHICH IS | | | CORRECT? PLEASE COORDINATE PLANS AND SHOW COMPLIANCE | | | WITH FBCM 307.2.3. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|