2009-05-19 13:56:42****CORRECTIONS****
 ****BUILDING REVIEW OF MECHANICAL PERMIT APPLICATION
 (FEMA REQUIREMENTS)***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENT FROM PREVIOUS LIST:
  
 1. PLEASE SEE FEMA GUIDELINES, ATTACHED, FOR MECHANICAL
 EQUIPMENT. PLEASE SHOW HOW EQUIPMENT WITH COMPLY WITH
 CITY OF WEST PALM BEACH MUNICIPAL CODE REQUIREMENTS FOR
 IMPROVEMENTS IN A FLOOD ZONE. 94-541-6.
  
 2ND REVIEW, NOT ADDRESSED. NO INFORMATION REGARDING
 DUCTWORK WAS PROVIDED. I HAVE HIGHLIGHTED PERTINENT
 PORTIONS, SPECIFICALLY:
  
 SECTION 3.1.2, COMPONENT PROTECTION REFERS TO THE
 IMPLEMENTATION OF DESIGN TECHNIQUES THAT PROTECT A
 COMPONENT LOCATED BELOW THE DFE FROM FLOOD DAMAGE BY
 PREVENTING FLOODWATER FROM ENTERING OR ACCUMULATING
 WITHIN THE SYSTEM COMPONENTS.
  
 SECTION 3.1.3 STATES THAT HVAC EQUIPMENT IS NOT
 "DESIGNED TO WITHSTAND INUNDATION BY FLOODWATER" OR
 "THE DYNAMIC FORCES OF HIGH VELOCITY FLOW."
  
 SECTION 3.1.5 STATES "SUPPORTING DISTRUBUTION SYSTEMS
 INCLUDE AIR DUCTS . . . ." IT ALSO STATES THAT THE
 "NFIP REQUIERS THAT AIR DUCTS IN HVAC SYSTEMS BE
 DESIGNED AND/OR LOCATED IN STRUCTURES IN SUCH A WAY THA
 TPREVENTS WATER FROM ENTERING OR ACCUMULATING WITH THE
 HVAC SYSTEM COMPONENTS DURING BASE FLOODING
 CONDITIONS." IT GOES ON TO SAY "LOCATING DUCTWORK BELOW
 THE DFE IS NOT PERMITTED UNLESS IT IS DESIGNED AND
 CONSTRUCTED SO THAT FLOODWATER WILL NOT ENTER OR
 ACCUMULATE WITHIN THE SYSTEM COMPONENTS." THE FOLLOWING
 PARAGRAPH STATES THAT THE NFIP DOES NOT RECOMMEND
 LOCATING DUCT WORK BELOW THE DFE IN ANY NEW STRUCTURE,
 BUT DOES GIVE GUIDELINES IF DUCT WORK MUST BE INSTALLED
 BELOW THE DFE. IT ALSO STATES THAT THERE IS NO KNOWN
 COST-EFFECTIVE TECHNIQUE FOR DESIGNING AIR DUCTS TO
 KEEP FLOODWATER FROM ENTERING OR ACCUMULATING WITHIN
 THE SYSTEM COMPONENTS DURING INUNDATION BY FLOODWATERS.
 IF DUCTWORK IS INSTALLED BELOW DFE, "THE MATERIAL USED
 FOR THE DUCTS MUST BE IPERMEABLE AND WATERTIGHT (SUCH
 AS WELDED SEAMLESS DUCTWORK OR LARGE DIAMETER PVC
 PIPE)."
  
 SEE THE NOTE ON THE SIDE OF PAGE 3.1-14, STATES THAT
 THE GUIDELINES ARE FOR DUCT SEGMENTS WHICH ARE
 WATERTIGHT AND WHICH TERMINATE ABOVE THE DFE. DUCT
 SEGMENTS WITH OPENINGS BELOW THE DFE OR THAT TERMINATE
 BELOW THE DFE ARE NOT PERMITTED UNDER THE NFIP.
  
 THE PLAN PROVIDED PROPOSES TO INSTALL THE UNIT AT 13'6"
 AND THE DUCTWORK 6" "ABOVE EARTH." THE PROPOSED
 ELEVATION FOR DUCTWORK MUST BE GIVEN IN RELATION TO
 DFE. WILL THE DUCT BE BELOW DFE? PLEASE SEE THE NOTE
 WHICH STATES THAT THIS IS NOT PERMITTED.
  
 PLEASE SEE THE ENTIRE DOCUMENT FOR MORE INFORMATION
 REGARDING INSTALLATION OF HVAC EQUIPMENT. IF SEGMENTS
 OF THE DUCTWORK ARE PROPOSED BELOW DFE, PROVIDE ENOUGH
 INFORMATION (SPEC SHEETS, CALCULATIONS, ETC.) TO SHOW
 THAT THEY MEET THE REQUIREMENTS TO RESIST WATER AND
 DYNAMIC FORCES. IF SEGMENTS ARE PROPOSED BELOW DFE,
 PROVIDE A SECTION SHOWING DUCTWORK AND ELEVATION AT
 EACH POINT, AS WELL AS TERMINATION ELEVATION.
  
  