Plan Review Notes
Plan Review Notes For Permit 09020075
Permit Number 09020075
Review Stop B
Sequence Number 6
Notes
Date Text
2009-07-06 16:30:14****CORRECTIONS****
 ****REVISION, SHEET 1****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THE DETAIL SECTION D-D DOES NOT SPECIFY
 HAND/GUARDRAIL HEIGHT. AS THE HEIGHT OF FINISHED FLOOR
 IS OVER 30", A GUARDRAIL IS REQUIRED. PLEASE SPECIFY
 HEIGHT, FBC R 311.5.1, FBC R 312.1.
  
 2. FBC R 311.5.3.3, NOSING OF APPROXIMATELY 1" IS
 REQUIRED. THE PLAN STATES THAT THERE IS A 1 1/2" NOSE,
 BUT A NOSING SHOWN ON THE DETAIL SECTION D-D. PLEASE
 INCORPORATE THE NOSING INTO THE DETAIL. PLEASE ALSO
 PROVIDE JUSTIFICATION AS TO WHY THIS IS SPECIFIED AS 1
 1/2" RATHER THAN 1". 1/2" IS 50% MORE THAN THE
 DIMENSION SPECIFIED IN THE CODE.
  
 3. A HANDRAIL/GUARDRAIL IS REQUIRED AT BOTH STAIRS, BUT
 IS SHOWN AT ONLY ONE STAIR. PLEASE PROVIDE A DETAIL FOR
 THE SECOND STAIR. FBC R 311.5, 312.1.
  
 4. THE VENTILATION REQUIREMENT WAS NOT ADDRESSED
 (COMMENT FROM FIRST PLAN REVIEW) AND WAS THEREFORE
 REDLINED, FBC R 408.1. AS THIS SHEET IS TO BE REVISED,
 PLEASE INCORPORATE THIS CHANGE (VENTILATION TO BE
 WITHIN 3' OF THE CORNERS) INTO THE PLAN.
  
 5. THIS PERMIT WAS ISSUED WITH PROVISO, ACCESS REQUIRED
 FOR UNDER-FLOOR SPACE FBC R408.3. PLEASE INDICATE
 LOCATION.
  
 6. PLEASE PROVIDE A REVISED SITE PLAN SHOWING FINAL
 STAIR LOCATION IN RELATION TO THE HOUSE. FBC*106.
  
  