| 2009-07-06 16:30:14 | ****CORRECTIONS**** |
| | ****REVISION, SHEET 1**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. THE DETAIL SECTION D-D DOES NOT SPECIFY |
| | HAND/GUARDRAIL HEIGHT. AS THE HEIGHT OF FINISHED FLOOR |
| | IS OVER 30", A GUARDRAIL IS REQUIRED. PLEASE SPECIFY |
| | HEIGHT, FBC R 311.5.1, FBC R 312.1. |
| | |
| | 2. FBC R 311.5.3.3, NOSING OF APPROXIMATELY 1" IS |
| | REQUIRED. THE PLAN STATES THAT THERE IS A 1 1/2" NOSE, |
| | BUT A NOSING SHOWN ON THE DETAIL SECTION D-D. PLEASE |
| | INCORPORATE THE NOSING INTO THE DETAIL. PLEASE ALSO |
| | PROVIDE JUSTIFICATION AS TO WHY THIS IS SPECIFIED AS 1 |
| | 1/2" RATHER THAN 1". 1/2" IS 50% MORE THAN THE |
| | DIMENSION SPECIFIED IN THE CODE. |
| | |
| | 3. A HANDRAIL/GUARDRAIL IS REQUIRED AT BOTH STAIRS, BUT |
| | IS SHOWN AT ONLY ONE STAIR. PLEASE PROVIDE A DETAIL FOR |
| | THE SECOND STAIR. FBC R 311.5, 312.1. |
| | |
| | 4. THE VENTILATION REQUIREMENT WAS NOT ADDRESSED |
| | (COMMENT FROM FIRST PLAN REVIEW) AND WAS THEREFORE |
| | REDLINED, FBC R 408.1. AS THIS SHEET IS TO BE REVISED, |
| | PLEASE INCORPORATE THIS CHANGE (VENTILATION TO BE |
| | WITHIN 3' OF THE CORNERS) INTO THE PLAN. |
| | |
| | 5. THIS PERMIT WAS ISSUED WITH PROVISO, ACCESS REQUIRED |
| | FOR UNDER-FLOOR SPACE FBC R408.3. PLEASE INDICATE |
| | LOCATION. |
| | |
| | 6. PLEASE PROVIDE A REVISED SITE PLAN SHOWING FINAL |
| | STAIR LOCATION IN RELATION TO THE HOUSE. FBC*106. |
| | |
| | |