| Plan Review Notes For Permit 09020075 |
| Permit Number |
09020075 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-02-10 09:20:59 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} AN ELECTRICAL PERMIT IS REQUIRED FOR THE SCOPE OF | | | WORK PURPOSED. 105.1 FBC AS AMENDED. | | | | | | 2} PLEASE SUBMIT A SITE PLAN INDICATING THE LOCATION OF | | | THE METER, MAIN DISCONNECT {WITH AIC RATING}. PER | | | ARTICLE 550 NEC. | | | | | | 3} PROVIDE ELECTRICAL PLANS FOR THE WIRING OF THE A/C | | | UNIT APPLICATION # 09020078. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|