Plan Review Notes
Plan Review Notes For Permit 09020057
Permit Number 09020057
Review Stop E
Sequence Number 1
Notes
Date Text
2009-02-09 09:22:26 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE DESCRIPTION ON THE APPLICATION INDICATES LIGHT
 ARE TO BE SET BUT NO PLANS WERE SUBMITTED. LOCATE THE
 POLES ON A PLAN AND SUBMIT SPECIFICATIONS FOR THE
 POLES. 106.1.1 FBC.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  