| Plan Review Notes For Permit 09020052 |
| Permit Number |
09020052 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-04-27 10:12:10 | | | | | | | | | | PASSED/PROVISO | | | | | | APPROVAL CONTINGENT ON INFORMATION RECEIVED FOR GREASE | | | INTERCEPTOR REQUIREMENT. IF A GREASE INTERCEPTOR IS | | | REQUIRED, THEN REVISION SHALL BE REQUIRED AS WELL AS A | | | SEPARATE PERMIT FOR THE GREASE INTERCEPTOR. | | | | | | SHT WP/A-7.2 DETAIL B/WP-A-7.2 INDICATES WEEP DRAIN AND | | | STATES "SEE PLUMB.". NO INFORMATION IS INDICATED ON THE | | | PLUMBING SHEETS. PLEASE SUBMIT A DETAIL FOR THE DRAIN | | | SHOWING HOW THE PIPING CONNECTS TO THE WEEP DRAIN. | | | SUBMIT MANUF. SPECIFICATIONS FOR THE WEEP DRAIN. | | | INDICATE HOW MANY WEEP DRAIN CONNECTIONS ARE THERE AND | | | EXACTLY WHERE THE CONNECTIONS WILL BE LOCATED. SECTION | | | 106.1.2. (NOT SHOWN ON PLUMBING OR CIVIL SHEETS). - | | | INFORMATION IS REQUIRED PRIOR TO INSPECTION. | | | | | | | | | SHT P-3 ROOF DRAINAGE RISER DIAGRAMS. ROD/1 IS SHOWN AS | | | 3 INCH ROD ON THE RISER DIAGRAM BUT AS 4 INCH ROD ON | | | SHT P-2. ALSO THE HORIZONTAL PIPING SHALL BE 4" PER | | | TABLE 1106.3. PLEASE CORRELATE AND SHOW THE PIPE SIZE. | | | SECTION 106.1.1. -- REVISION REQUIRED PRIOR TO | | | INSPECTION. | | | | | | . |
|