Plan Review Notes
Plan Review Notes For Permit 09020052
Permit Number 09020052
Review Stop P
Sequence Number 2
Notes
Date Text
2009-04-27 10:12:10 
  
  
 PASSED/PROVISO
  
 APPROVAL CONTINGENT ON INFORMATION RECEIVED FOR GREASE
 INTERCEPTOR REQUIREMENT. IF A GREASE INTERCEPTOR IS
 REQUIRED, THEN REVISION SHALL BE REQUIRED AS WELL AS A
 SEPARATE PERMIT FOR THE GREASE INTERCEPTOR.
  
 SHT WP/A-7.2 DETAIL B/WP-A-7.2 INDICATES WEEP DRAIN AND
 STATES "SEE PLUMB.". NO INFORMATION IS INDICATED ON THE
 PLUMBING SHEETS. PLEASE SUBMIT A DETAIL FOR THE DRAIN
 SHOWING HOW THE PIPING CONNECTS TO THE WEEP DRAIN.
 SUBMIT MANUF. SPECIFICATIONS FOR THE WEEP DRAIN.
 INDICATE HOW MANY WEEP DRAIN CONNECTIONS ARE THERE AND
 EXACTLY WHERE THE CONNECTIONS WILL BE LOCATED. SECTION
 106.1.2. (NOT SHOWN ON PLUMBING OR CIVIL SHEETS). -
 INFORMATION IS REQUIRED PRIOR TO INSPECTION.
  
  
 SHT P-3 ROOF DRAINAGE RISER DIAGRAMS. ROD/1 IS SHOWN AS
 3 INCH ROD ON THE RISER DIAGRAM BUT AS 4 INCH ROD ON
 SHT P-2. ALSO THE HORIZONTAL PIPING SHALL BE 4" PER
 TABLE 1106.3. PLEASE CORRELATE AND SHOW THE PIPE SIZE.
 SECTION 106.1.1. -- REVISION REQUIRED PRIOR TO
 INSPECTION.
  
 .