Plan Review Notes
Plan Review Notes For Permit 09020052
Permit Number 09020052
Review Stop P
Sequence Number 1
Notes
Date Text
2009-02-25 14:45:31DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 CHAPTER 13
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MINICIPAL CODE
  
 1. SHTS IR-1 THRU IR-4 INDICATE THE LOCATION OF THE
 WATER SOURCE(S), METER(S), BACKFLOW(S), CONTROLLER(S) &
 RAIN SENSOR(S). SECTIONS 106.1.2, 608.13.2, 608.13.5 &
 APPENDIX F PART II (J) WITH FS 373.62.
  
 2. SHTS IR-1 THRU IR-5 THE LANDSCAPE ARCHITECT BUSINESS
 LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), IS
 MISSING FROM THE TITLE BLOCKS. FAC 61G1-16.004(2) & FS
 481.306. ALSO THE DATE THE SEAL AND SIGNATURE ARE
 AFFIXED SHALL APPEAR BY THE SIGNATURE ON EACH SHEET.
 FAC 61G1-16.003, 61G1-16.004(5) & FS 481.306.
  
 3. SHT LS-1.0 CALCULATIONS FOR EGRESS CAPICITY
 INDICATES 15 SF PER PERSON. PER TABLE 1004.1.2
 OCCUPANCY A3 15 SF PER PERSON IS FOR UNCONSENTRATED,
 (TABLES & CHAIRS). SINCE THERE CAN ALSO BE STANDING
 SPACE WITH OUT THE TABLES & CHAIRS, THE CALCULATIONS
 SHALL INDICATE THE WORST CASE SCENARIO, STANDING SPACE.
 3005 SF @ 5 SF PER PERSON EQUALS 601. TOILET FACILITIES
 PER TABLE 403.1 601 DIVIDED BY 2 EQUALS 301 FOR MALE
 AND 301 FOR FEMALE. FOR MALE THE WATER CLOSET
 REQUIREMENTS ARE 3, 301 DIVIDED BY 125 EQUALS 2.408
 ROUNDED UP TO 3. FOR FEMALE THE WATER CLOSET
 REQUIREMENTS ARE 5, 301 DIVIDED BY 65 EQUALS 4.63
 ROUNDED UP TO 5. ONE MORE WATER CLOSET IS REQUIRED FOR
 THE FEMALE TOILET ROOM.
  
 4. SHT LS-1.0 TWO DRINKING FOUNTAINS ARE REQUIRED PER
 TABLE 403.1. A HIGH/LOW DRINKING FOUNTAIN IS CONSIDERED
 AS ONE DRINKING FOUNTAIN AS THERE IS ONLY ONE WATER
 SUPPLY AND ONE TRAP AND WASTE ARM. SECTIONS 602.2 &
 1002.1. PLEASE INDICATE THE LOCATION OF THE 2ND
 DRINKING FOUNTAIN. (ALSO SEE SECTION 410.1.)
  
 5. SHT LS-1.0 SHOWS CATERING. MORE INFORMATION IS
 REQUIRED. WILL THERE BE FOOD PREP AT THE CATERING. -- A
 GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT THE
 UTILITY DEPT. INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT HOLLY MCGRATH, LABORATORY
 SUPERVISOR BY PHONE (561) 822-2271, BY FAX (5610
 822-2279 OR BY E-MAIL [email protected]. ARTICLE III
 SECTION 90-124(7). A WRITTEN DETERMINATION SHALL BE
 SUBMITTED INDICATING THE RESULTS FROM UTILITY DEPT.
  
 6. SHTS WP/A-3, WP/A-5.0 & WP/A-5.1. SUBMIT A DETAIL
 FOR THE EMERGENCY OVERFLOW SCUPPERS. SHOW THE HEIGHT &
 WIDTH OF THE OPENING AS WELL AS THE DISTANCE FROM THE
 ROOF TO THE FLOW LINE OF THE SCUPPER. SECTIONS 1503.4.3
 & TABLE 1106.7.
  
 7. SHT WP/A-7.2 DETAIL B/WP-A-7.2 INDICATES WEEP DRAIN
 AND STATES "SEE PLUMB.". NO INFORMATION IS INDICATED ON
 THE PLUMBING SHEETS. PLEASE SUBMIT A DETAIL FOR THE
 DRAIN SHOWING HOW THE PIPING CONNECTS TO THE WEEP
 DRAIN. SUBMIT MANUF. SPECIFICATIONS FOR THE WEEP DRAIN.
 INDICATE HOW MANY WEEP DRAIN CONNECTIONS ARE THERE AND
 EXACTLY WHERE THE CONNECTIONS WILL BE LOCATED. SECTION
 106.1.2. (NOT SHOWN ON PLUMBING OR CIVIL SHEETS).
  
 8. SHT P-3 ROOF DRAINAGE RISER DIAGRAMS. ROD/1 IS SHOWN
 AS 3 INCH ROD ON THE RISER DIAGRAM BUT AS 4 INCH ROD ON
 SHT P-2. ALSO THE HORIZONTAL PIPING SHALL BE 4" PER
 TABLE 1106.3. PLEASE CORRELATE AND SHOW THE PIPE SIZE.
 SECTION 106.1.1.
  
 9. SHT P-3 WATER RISER DIAGRAM. IDENTIFY THE FITTINGS
 AT THE TOP OF EACH FIXTURE SUPPLY. THIS IS NOT
 INDICATED ON THE PLUMBING SYMBOL LEGEND. SECTION
 106.1.2.. (MORE INFORMATION REQUIRED). IF THE FITINGS
 ARE AIR CHAMBERS, THEY ARE NOT APPROVED AND SHALL BE
 DELETED. SECTION 604.9 & PDI-WH 201.
  
 10. SHT P-7 PLUMBING SPECIFICATIONS. ITEM NUMBER 8. AIR
 CHAMBERS ARE NOT APPROVED AND REFERENCE TO AIR CHAMBERS
 SHALL BE DELETED. SECTION 604.9 & PDI-WH 201.
  
 11. THE ENERGENCY CALCULATIONS SUBMITTED SHOW
 CALCULATION FOR WATER HEATERS BUT THERE ARE TWO
 INSTA-HOT WATER HEATERS INDICATED ON SHEETS P-3 & P-5.
 ALSO THERE IS NOT INFORMATION FOR THE PIPING
 INSULATION. PLEASE SHOW COMPLIANCE WITH CHAPTER 13 OF
 THE BUILDING CODE. ENERGY EFFICIENCY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved