| Date |
Text |
| 2009-02-25 14:45:31 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 CHAPTER 13 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY WPB MINICIPAL CODE |
| | |
| | 1. SHTS IR-1 THRU IR-4 INDICATE THE LOCATION OF THE |
| | WATER SOURCE(S), METER(S), BACKFLOW(S), CONTROLLER(S) & |
| | RAIN SENSOR(S). SECTIONS 106.1.2, 608.13.2, 608.13.5 & |
| | APPENDIX F PART II (J) WITH FS 373.62. |
| | |
| | 2. SHTS IR-1 THRU IR-5 THE LANDSCAPE ARCHITECT BUSINESS |
| | LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), IS |
| | MISSING FROM THE TITLE BLOCKS. FAC 61G1-16.004(2) & FS |
| | 481.306. ALSO THE DATE THE SEAL AND SIGNATURE ARE |
| | AFFIXED SHALL APPEAR BY THE SIGNATURE ON EACH SHEET. |
| | FAC 61G1-16.003, 61G1-16.004(5) & FS 481.306. |
| | |
| | 3. SHT LS-1.0 CALCULATIONS FOR EGRESS CAPICITY |
| | INDICATES 15 SF PER PERSON. PER TABLE 1004.1.2 |
| | OCCUPANCY A3 15 SF PER PERSON IS FOR UNCONSENTRATED, |
| | (TABLES & CHAIRS). SINCE THERE CAN ALSO BE STANDING |
| | SPACE WITH OUT THE TABLES & CHAIRS, THE CALCULATIONS |
| | SHALL INDICATE THE WORST CASE SCENARIO, STANDING SPACE. |
| | 3005 SF @ 5 SF PER PERSON EQUALS 601. TOILET FACILITIES |
| | PER TABLE 403.1 601 DIVIDED BY 2 EQUALS 301 FOR MALE |
| | AND 301 FOR FEMALE. FOR MALE THE WATER CLOSET |
| | REQUIREMENTS ARE 3, 301 DIVIDED BY 125 EQUALS 2.408 |
| | ROUNDED UP TO 3. FOR FEMALE THE WATER CLOSET |
| | REQUIREMENTS ARE 5, 301 DIVIDED BY 65 EQUALS 4.63 |
| | ROUNDED UP TO 5. ONE MORE WATER CLOSET IS REQUIRED FOR |
| | THE FEMALE TOILET ROOM. |
| | |
| | 4. SHT LS-1.0 TWO DRINKING FOUNTAINS ARE REQUIRED PER |
| | TABLE 403.1. A HIGH/LOW DRINKING FOUNTAIN IS CONSIDERED |
| | AS ONE DRINKING FOUNTAIN AS THERE IS ONLY ONE WATER |
| | SUPPLY AND ONE TRAP AND WASTE ARM. SECTIONS 602.2 & |
| | 1002.1. PLEASE INDICATE THE LOCATION OF THE 2ND |
| | DRINKING FOUNTAIN. (ALSO SEE SECTION 410.1.) |
| | |
| | 5. SHT LS-1.0 SHOWS CATERING. MORE INFORMATION IS |
| | REQUIRED. WILL THERE BE FOOD PREP AT THE CATERING. -- A |
| | GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT THE |
| | UTILITY DEPT. INDUSTRIAL PRETREATMENT, ENVIRONMENTAL |
| | COMPLIANCE. PLEASE CONTACT HOLLY MCGRATH, LABORATORY |
| | SUPERVISOR BY PHONE (561) 822-2271, BY FAX (5610 |
| | 822-2279 OR BY E-MAIL [email protected]. ARTICLE III |
| | SECTION 90-124(7). A WRITTEN DETERMINATION SHALL BE |
| | SUBMITTED INDICATING THE RESULTS FROM UTILITY DEPT. |
| | |
| | 6. SHTS WP/A-3, WP/A-5.0 & WP/A-5.1. SUBMIT A DETAIL |
| | FOR THE EMERGENCY OVERFLOW SCUPPERS. SHOW THE HEIGHT & |
| | WIDTH OF THE OPENING AS WELL AS THE DISTANCE FROM THE |
| | ROOF TO THE FLOW LINE OF THE SCUPPER. SECTIONS 1503.4.3 |
| | & TABLE 1106.7. |
| | |
| | 7. SHT WP/A-7.2 DETAIL B/WP-A-7.2 INDICATES WEEP DRAIN |
| | AND STATES "SEE PLUMB.". NO INFORMATION IS INDICATED ON |
| | THE PLUMBING SHEETS. PLEASE SUBMIT A DETAIL FOR THE |
| | DRAIN SHOWING HOW THE PIPING CONNECTS TO THE WEEP |
| | DRAIN. SUBMIT MANUF. SPECIFICATIONS FOR THE WEEP DRAIN. |
| | INDICATE HOW MANY WEEP DRAIN CONNECTIONS ARE THERE AND |
| | EXACTLY WHERE THE CONNECTIONS WILL BE LOCATED. SECTION |
| | 106.1.2. (NOT SHOWN ON PLUMBING OR CIVIL SHEETS). |
| | |
| | 8. SHT P-3 ROOF DRAINAGE RISER DIAGRAMS. ROD/1 IS SHOWN |
| | AS 3 INCH ROD ON THE RISER DIAGRAM BUT AS 4 INCH ROD ON |
| | SHT P-2. ALSO THE HORIZONTAL PIPING SHALL BE 4" PER |
| | TABLE 1106.3. PLEASE CORRELATE AND SHOW THE PIPE SIZE. |
| | SECTION 106.1.1. |
| | |
| | 9. SHT P-3 WATER RISER DIAGRAM. IDENTIFY THE FITTINGS |
| | AT THE TOP OF EACH FIXTURE SUPPLY. THIS IS NOT |
| | INDICATED ON THE PLUMBING SYMBOL LEGEND. SECTION |
| | 106.1.2.. (MORE INFORMATION REQUIRED). IF THE FITINGS |
| | ARE AIR CHAMBERS, THEY ARE NOT APPROVED AND SHALL BE |
| | DELETED. SECTION 604.9 & PDI-WH 201. |
| | |
| | 10. SHT P-7 PLUMBING SPECIFICATIONS. ITEM NUMBER 8. AIR |
| | CHAMBERS ARE NOT APPROVED AND REFERENCE TO AIR CHAMBERS |
| | SHALL BE DELETED. SECTION 604.9 & PDI-WH 201. |
| | |
| | 11. THE ENERGENCY CALCULATIONS SUBMITTED SHOW |
| | CALCULATION FOR WATER HEATERS BUT THERE ARE TWO |
| | INSTA-HOT WATER HEATERS INDICATED ON SHEETS P-3 & P-5. |
| | ALSO THERE IS NOT INFORMATION FOR THE PIPING |
| | INSULATION. PLEASE SHOW COMPLIANCE WITH CHAPTER 13 OF |
| | THE BUILDING CODE. ENERGY EFFICIENCY. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |