Plan Review Notes
Plan Review Notes For Permit 09020052
Permit Number 09020052
Review Stop M
Sequence Number 1
Notes
Date Text
2009-03-03 08:54:28REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. AC-1: THE SUPPLY DUCT FOR AHU-1 SHOWS A 100 CFM
 REGISTER UPSTREAM OF THE DUCT SMOKE DETECTOR. THE
 REQUIRED SMOKE DETECTORS SHALL BE INSTALLED TO MONITOR
 THE ENTIRE AIRFLOW CONVEYED BY THE SYSTEM IN ACCORDANCE
 WITH FBC-M 606.3.PLEASE SHOW ALL SUPPLY OUTLETS
 DOWNSTREAM OF THE SMOKE DETECTOR.
  
 2. AC-1: THERE ARE MULTIPLE MANUAL AND MOTORIZED VOLUME
 DAMPERS SHOWN TO BE LOCATED ABOVE GYPSUM WALLBOARD
 CEILINGS IN LOBBY 101, RESTROOM 104 AND CATERING 106.
 ALSO DH-1 AND THE SMOKE DETECTOR FOR AHU-1. PLEASE SHOW
 HOW THESE ARE TO BE ACCESSED IN ACCORDANCE WITH FBC-M
 306.1 AND FBC-M 603.15.
  
 3. AC-1: THE AIRFLOW VOLUME AS SHOWN ON FLOOR PLAN FOR
 AHU-1 DOES NOT CORRESPOND WITH THE VOLUME SHOWN ON THE
 EQUIPMENT SCHEDULE. IT APPEARS THAT ONE OF THE A TYPE
 REGISTERS SERVING COMMUNITY ROOM 102 HAS THE CFM
 DESIGNATION TRANSPOSED TO READ 272 INSTEAD OF 727.
 PLEASE VERIFY AND CORRECT AS NECESSARY TO COORDINATE
 FLOOR PLAN WITH THE EQUIPMENT SCHEDULE. FBC-M 603.1,
 FBC-B 106.1.1.
  
 4. AC-1 AND AC-5: FLOOR PLAN SHOWS F-2 IN CATERING ROOM
 106 WHILE THIS FAN APPEARS TO BE DESIGNATED AS F-4 ON
 THE FAN SCHEDULE. PLEASE COORDINATE FLOOR PLANS AND
 EQUIPMENT SCHEDULES IN ACCORDANCE WITH FBC-B 106.1.1
 AND FBC-M 304.1.
  
 5. AC-2: THIS PAGE SHOWS A ROOF CURB ATTACHMENT DETAIL
 FOR F-1. HOWEVER, THERE IS NO INFORMATION REGARDING THE
 WIND RESISTANCE CAPABILITIES FOR F-1 ITSELF. THIS
 APPLIANCE IS EXPOSED TO WIND AND SHALL BE DESIGNED TO
 RESIST ANTICIPATED WIND PRESSURES IN ACCORDANCE WITH
 FBC-M 301.13.
  
 6. AC-2: ROOF CURB DETAIL NOTE #4 REFERS TO STRUCTURAL
 PLANS FOR ADDITIONAL DETAIL AND WIND LOAD ANALYSIS FOR
 ROOF CURBS. NO SUCH DETAIL OR INFORMATION COULD BE
 FOUND IN THE STRUCTURAL PLANS. PLEASE CLARIFY WHERE
 THIS INFORMATION CAN BE FOUND. FBC-M 301.13 AND FBC-B
 106.1.1.
  
 7. AC-2: ROOF CURB DETAIL NOTE #1`4 APPEARS TO BE
 MISLABELED AS NOTE #15 ON THE DETAIL DRAWING. PLEASE
 CORRECT AND COORDINATE THE DETAIL NOTES WITH THE DETAIL
 DRAWING IN ACCORDANCE WITH FBC-B 106.1.1.
  
 8. AC-3: PLEASE CLARIFY THE SIZE OF CRUSHED ROCK TO BE
 USED IN THE DRYWELL. DETAIL NOTE #4 IS UNCLEAR AND
 NEEDS CORRECTION. FBC-M 307.2.1 AND FBC-B 106.1.1.
  
 9. AC-4: THE CONDENSING UNIT MOUNTING DETAIL DOES NOT
 CORRESPOND WITH THE CONDENSING UNIT DETAIL FOUND IN
 STRUCTURAL PLANS. WHICH IS CORRECT? ALSO, PLEASE
 PROVIDE INFORMATION FROM CONDENSING UNIT MANUFACTURER
 SHOWING THESE APPLIANCES ARE DESIGNED FOR WIND
 RESISTANCE IN ACCORDANCE WITH FBC-M 301.13.
  
 10. ENERGY CALCULATIONS: NO COOLING LOAD CALCULATIONS
 COULD BE FOUND INTHIS SUBMISSION. THEREFORE A COMPLETE
 REVIEW OF THE ENERGY CALCULATIONS CANNOT BE PERFORMED
 AT THIS TIME. A COOLING LOAD CALCULATION SHALL BE
 PERFORMED FOR NEWLY INSTALLED UNITS, AND THIS
 CALCULATION SHALL BE ATTACHED TO THE CODE COMPLIANCE
 FORM (ENERGY CALCULATIONS) SUBMITTED TO THE BUILDING
 DEPARTMENT WHEN THE BUILDING IS PERMITTED IN ACCORDANCE
 WITH FBC-B 13-407.1.ABC.1.1.
  
 NOTE: IF ADDITIONAL TIME IS NEEDED TO ADDRESS THE WIND
 RESISTANCE REQUIREMENTS FOR OUTDOOR APPLIANCES, THIS
 ITEM WILL BE MADE INTO A PROVISO TO ALLOW PERMIT
 ISSUANCE WHILE THE NECESSARY DATA IS BEING COMPILED.
 PLEASE ADVISE AS PART OF THE WRITTEN RESPONSE FROM THE
 DESIGN TEAM IF THIS OPTION IS DESIRED.
  