| 2009-03-03 08:54:28 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. AC-1: THE SUPPLY DUCT FOR AHU-1 SHOWS A 100 CFM |
| | REGISTER UPSTREAM OF THE DUCT SMOKE DETECTOR. THE |
| | REQUIRED SMOKE DETECTORS SHALL BE INSTALLED TO MONITOR |
| | THE ENTIRE AIRFLOW CONVEYED BY THE SYSTEM IN ACCORDANCE |
| | WITH FBC-M 606.3.PLEASE SHOW ALL SUPPLY OUTLETS |
| | DOWNSTREAM OF THE SMOKE DETECTOR. |
| | |
| | 2. AC-1: THERE ARE MULTIPLE MANUAL AND MOTORIZED VOLUME |
| | DAMPERS SHOWN TO BE LOCATED ABOVE GYPSUM WALLBOARD |
| | CEILINGS IN LOBBY 101, RESTROOM 104 AND CATERING 106. |
| | ALSO DH-1 AND THE SMOKE DETECTOR FOR AHU-1. PLEASE SHOW |
| | HOW THESE ARE TO BE ACCESSED IN ACCORDANCE WITH FBC-M |
| | 306.1 AND FBC-M 603.15. |
| | |
| | 3. AC-1: THE AIRFLOW VOLUME AS SHOWN ON FLOOR PLAN FOR |
| | AHU-1 DOES NOT CORRESPOND WITH THE VOLUME SHOWN ON THE |
| | EQUIPMENT SCHEDULE. IT APPEARS THAT ONE OF THE A TYPE |
| | REGISTERS SERVING COMMUNITY ROOM 102 HAS THE CFM |
| | DESIGNATION TRANSPOSED TO READ 272 INSTEAD OF 727. |
| | PLEASE VERIFY AND CORRECT AS NECESSARY TO COORDINATE |
| | FLOOR PLAN WITH THE EQUIPMENT SCHEDULE. FBC-M 603.1, |
| | FBC-B 106.1.1. |
| | |
| | 4. AC-1 AND AC-5: FLOOR PLAN SHOWS F-2 IN CATERING ROOM |
| | 106 WHILE THIS FAN APPEARS TO BE DESIGNATED AS F-4 ON |
| | THE FAN SCHEDULE. PLEASE COORDINATE FLOOR PLANS AND |
| | EQUIPMENT SCHEDULES IN ACCORDANCE WITH FBC-B 106.1.1 |
| | AND FBC-M 304.1. |
| | |
| | 5. AC-2: THIS PAGE SHOWS A ROOF CURB ATTACHMENT DETAIL |
| | FOR F-1. HOWEVER, THERE IS NO INFORMATION REGARDING THE |
| | WIND RESISTANCE CAPABILITIES FOR F-1 ITSELF. THIS |
| | APPLIANCE IS EXPOSED TO WIND AND SHALL BE DESIGNED TO |
| | RESIST ANTICIPATED WIND PRESSURES IN ACCORDANCE WITH |
| | FBC-M 301.13. |
| | |
| | 6. AC-2: ROOF CURB DETAIL NOTE #4 REFERS TO STRUCTURAL |
| | PLANS FOR ADDITIONAL DETAIL AND WIND LOAD ANALYSIS FOR |
| | ROOF CURBS. NO SUCH DETAIL OR INFORMATION COULD BE |
| | FOUND IN THE STRUCTURAL PLANS. PLEASE CLARIFY WHERE |
| | THIS INFORMATION CAN BE FOUND. FBC-M 301.13 AND FBC-B |
| | 106.1.1. |
| | |
| | 7. AC-2: ROOF CURB DETAIL NOTE #1`4 APPEARS TO BE |
| | MISLABELED AS NOTE #15 ON THE DETAIL DRAWING. PLEASE |
| | CORRECT AND COORDINATE THE DETAIL NOTES WITH THE DETAIL |
| | DRAWING IN ACCORDANCE WITH FBC-B 106.1.1. |
| | |
| | 8. AC-3: PLEASE CLARIFY THE SIZE OF CRUSHED ROCK TO BE |
| | USED IN THE DRYWELL. DETAIL NOTE #4 IS UNCLEAR AND |
| | NEEDS CORRECTION. FBC-M 307.2.1 AND FBC-B 106.1.1. |
| | |
| | 9. AC-4: THE CONDENSING UNIT MOUNTING DETAIL DOES NOT |
| | CORRESPOND WITH THE CONDENSING UNIT DETAIL FOUND IN |
| | STRUCTURAL PLANS. WHICH IS CORRECT? ALSO, PLEASE |
| | PROVIDE INFORMATION FROM CONDENSING UNIT MANUFACTURER |
| | SHOWING THESE APPLIANCES ARE DESIGNED FOR WIND |
| | RESISTANCE IN ACCORDANCE WITH FBC-M 301.13. |
| | |
| | 10. ENERGY CALCULATIONS: NO COOLING LOAD CALCULATIONS |
| | COULD BE FOUND INTHIS SUBMISSION. THEREFORE A COMPLETE |
| | REVIEW OF THE ENERGY CALCULATIONS CANNOT BE PERFORMED |
| | AT THIS TIME. A COOLING LOAD CALCULATION SHALL BE |
| | PERFORMED FOR NEWLY INSTALLED UNITS, AND THIS |
| | CALCULATION SHALL BE ATTACHED TO THE CODE COMPLIANCE |
| | FORM (ENERGY CALCULATIONS) SUBMITTED TO THE BUILDING |
| | DEPARTMENT WHEN THE BUILDING IS PERMITTED IN ACCORDANCE |
| | WITH FBC-B 13-407.1.ABC.1.1. |
| | |
| | NOTE: IF ADDITIONAL TIME IS NEEDED TO ADDRESS THE WIND |
| | RESISTANCE REQUIREMENTS FOR OUTDOOR APPLIANCES, THIS |
| | ITEM WILL BE MADE INTO A PROVISO TO ALLOW PERMIT |
| | ISSUANCE WHILE THE NECESSARY DATA IS BEING COMPILED. |
| | PLEASE ADVISE AS PART OF THE WRITTEN RESPONSE FROM THE |
| | DESIGN TEAM IF THIS OPTION IS DESIRED. |
| | |