| 2009-02-27 13:28:27 | ***DENIED*** |
| | |
| | 1) CLEARLY IDENTIFY HOW WORK WILL IMPACT EXISTING FIRE |
| | HYDRANTS ON CIVIL SHEETS. SEVERAL OF THE DEMOLITION AND |
| | WATER PLANS DON'T SEEM TO PROVIDE INFORMATION RELEVANT |
| | TO WATER SUPPLY. |
| | |
| | 2) OCCUPANT LOAD SIGNS TO BE POSTED AT APPLICABLE |
| | LOCATIONS. CONTACT THE BUREAU OF FIRE PREVENTION AT |
| | (561) 804-4756 FOR ASSISTANCE. |
| | |
| | 3) A KNOX BOX IS REQUIRED TO BE INSTALLED FOR AFTER |
| | NORMAL BUSINESS HOURS EMERGENCY RESPONSES AND ACCESS TO |
| | BUILDING. |
| | |
| | 4) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE |
| | SPRINKLER AND FIRE ALARM SYSTEMS PRIOR TO EQUIPMENT |
| | INSTALLATION. ADDITIONALLY, THE FIRE SPRINKLER LAYOUT |
| | IS REQUIRED UNDER THIS PERMIT APPLICATION. MANUFACTURER |
| | SPECIFICATION SHEETS AND CALCULATIONS WILL BE REQUIRED |
| | AT THE TIME OF SEPARATE PERMITTING FOR EACH SYSTEM. |
| | |
| | 5) THE BUILDING SEEMS TO SUGGEST A COMPLETE SMOKE |
| | DETECTION SYSTEM WITH NO COVERAGE SHOWN IN THE |
| | ELECTRICAL ROOM. |
| | |
| | 6) ALL MEANS OF EGRESS AND EXTERIOR WALKING SURFACES |
| | SHALL BE SLIP RESISTANT. |
| | |
| | 7) SHEET WP A-8.0 INDICATES THE MINIMUM INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILING USING NFPA 101, |
| | SEC. 36.3.3.2 FOR MERCANTILE OCCUPANCIES. BUILDING USE |
| | HAS BEEN IDENTIFIED AS ASSEMBLY IN THE PLANS. |
| | |
| | 8) THE BUILDING ADDRESS IS ILLUSTRATED ON SHEET WP |
| | A-5.1. IN ADDITION TO THE MINIMUM HEIGHT REQUIREMENT OF |
| | 6" FOR COMMERCIAL BUILDINGS, THE WIDTH SHALL BE MINIMUM |
| | 1" AND THE NUMBER SHALL CONTRAST WITH THE BACKGROUND. |
| | THE ADDRESS IS TO BE VISIBLE FROM THE CENTER LINE OF |
| | THE STREET. |
| | |
| | 9) DUCT SMOKE DETECTORS SHALL BE TIED INTO THE BUILDING |
| | FIRE ALARM AND INITIATE A GENERAL FIRE ALARM IN |
| | ACCORDANCE WITH LOCAL REQUIREMENTS. SINGLE MOUNTED |
| | DETECTORS TO BE INSTALLED IN THE SUPPLY DUCT. SHEETS |
| | AC-3, AC-4 AND WP FA-1.0, NOTE 8. |
| | |
| | 10) SHEET E-7.0 INDICATES THE CONNECTION TO MOTORIZED |
| | EGRESS DOORS. PLEASE PROVIDE MORE INFORMATION REGARDING |
| | ANY IMPACT ON NORMAL EXITING OF BUILDING. |
| | |
| | 11) THE FIRE ALARM RISER AND LEGEND PROVIDES NO |
| | INFORMATION REGARDING SUPERVISION OF FIRE SPRINKLER |
| | EQUIPMENT. (FLOWS AND TAMPERS) |
| | |
| | 12) FIRE ALARM SYSTEM TO BE UL CERTIFICATED FOR CENTRAL |
| | STATION SERVICE. WORK SHALL COMPLY WITH NFPA 72, 2002. |
| | |
| | 13) FIRE SPRINKLER WORK TO COMPLY WITH NFPA 13, 2002. |
| | |
| | 14) PLANS DON'T APPEAR TO PROVIDE INFORMATION REGARDING |
| | THE LOCATION OF THE DOUBLE CHECK DETECTOR ASSEMBLY AND |
| | FIRE DEPARTMENT CONNECTION. |
| | |
| | |
| | MIKE WENNERGREN, ASST. FIRE MARSHAL |
| | FIRE PLAN REVIEW |
| | FIRE PREVENTION (561) 804-4756 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |