2009-02-27 13:28:27***DENIED***
  
 1) CLEARLY IDENTIFY HOW WORK WILL IMPACT EXISTING FIRE
 HYDRANTS ON CIVIL SHEETS. SEVERAL OF THE DEMOLITION AND
 WATER PLANS DON'T SEEM TO PROVIDE INFORMATION RELEVANT
 TO WATER SUPPLY.
  
 2) OCCUPANT LOAD SIGNS TO BE POSTED AT APPLICABLE
 LOCATIONS. CONTACT THE BUREAU OF FIRE PREVENTION AT
 (561) 804-4756 FOR ASSISTANCE.
  
 3) A KNOX BOX IS REQUIRED TO BE INSTALLED FOR AFTER
 NORMAL BUSINESS HOURS EMERGENCY RESPONSES AND ACCESS TO
 BUILDING.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS PRIOR TO EQUIPMENT
 INSTALLATION. ADDITIONALLY, THE FIRE SPRINKLER LAYOUT
 IS REQUIRED UNDER THIS PERMIT APPLICATION. MANUFACTURER
 SPECIFICATION SHEETS AND CALCULATIONS WILL BE REQUIRED
 AT THE TIME OF SEPARATE PERMITTING FOR EACH SYSTEM.
  
 5) THE BUILDING SEEMS TO SUGGEST A COMPLETE SMOKE
 DETECTION SYSTEM WITH NO COVERAGE SHOWN IN THE
 ELECTRICAL ROOM.
  
 6) ALL MEANS OF EGRESS AND EXTERIOR WALKING SURFACES
 SHALL BE SLIP RESISTANT.
  
 7) SHEET WP A-8.0 INDICATES THE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING USING NFPA 101,
 SEC. 36.3.3.2 FOR MERCANTILE OCCUPANCIES. BUILDING USE
 HAS BEEN IDENTIFIED AS ASSEMBLY IN THE PLANS.
  
 8) THE BUILDING ADDRESS IS ILLUSTRATED ON SHEET WP
 A-5.1. IN ADDITION TO THE MINIMUM HEIGHT REQUIREMENT OF
 6" FOR COMMERCIAL BUILDINGS, THE WIDTH SHALL BE MINIMUM
 1" AND THE NUMBER SHALL CONTRAST WITH THE BACKGROUND.
 THE ADDRESS IS TO BE VISIBLE FROM THE CENTER LINE OF
 THE STREET.
  
 9) DUCT SMOKE DETECTORS SHALL BE TIED INTO THE BUILDING
 FIRE ALARM AND INITIATE A GENERAL FIRE ALARM IN
 ACCORDANCE WITH LOCAL REQUIREMENTS. SINGLE MOUNTED
 DETECTORS TO BE INSTALLED IN THE SUPPLY DUCT. SHEETS
 AC-3, AC-4 AND WP FA-1.0, NOTE 8.
  
 10) SHEET E-7.0 INDICATES THE CONNECTION TO MOTORIZED
 EGRESS DOORS. PLEASE PROVIDE MORE INFORMATION REGARDING
 ANY IMPACT ON NORMAL EXITING OF BUILDING.
  
 11) THE FIRE ALARM RISER AND LEGEND PROVIDES NO
 INFORMATION REGARDING SUPERVISION OF FIRE SPRINKLER
 EQUIPMENT. (FLOWS AND TAMPERS)
  
 12) FIRE ALARM SYSTEM TO BE UL CERTIFICATED FOR CENTRAL
 STATION SERVICE. WORK SHALL COMPLY WITH NFPA 72, 2002.
  
 13) FIRE SPRINKLER WORK TO COMPLY WITH NFPA 13, 2002.
  
 14) PLANS DON'T APPEAR TO PROVIDE INFORMATION REGARDING
 THE LOCATION OF THE DOUBLE CHECK DETECTOR ASSEMBLY AND
 FIRE DEPARTMENT CONNECTION.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  