2009-03-02 14:55:33 
  
  
  
  
 APPLICATION #09020052 ELECTRICAL PLAN REVIEW
 101 S. FLAGLER DRIVE 2/27/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SEE BUILDING COMMENT (# 6) REGARDING FS 255.2575.
 INDICATE RATING SYSTEM AND LEVEL DESIGNED TOO.
  
 THESE COMMENTS ARE REGARDING THE RISER DIAGRAM ON SHEET
 E-4.0.
  
 2}THE EQUIPMENT GROUND BETWEEN THE TRANSFORMER AND
 "SWBD-WP" CREATES A PARALLEL PATH TO GROUND WITH THE
 NEUTRAL AND MUST BE REMOVED. AN ISOLATED NEUTRAL AND
 EQUIPMENT GROUND ARE TO BE RAN FROM THE FIRST MEANS OF
 DISCONNECT. 250.6.
  
 3} THE FEED FOR PANEL "WF" FROM "PSL" IS 3-#6 CU. PSL
 SCHEDULE CIRCUIT 43, 45,47 DO NOT INDICATE A WIRE OR
 CONDUIT SIZE, LIST SAME 408.4, AND HAS 100 AMP OCP IN
 VIOLATION OF 310.16 (MAX 65 AMPS) FOR THOSE CONDUCTORS.
  
 4} THE SOLAR PANEL SYSTEM FEED FROM "SWBD-WP" IS FROM A
 50 AMP BREAKER (ALSO A 50 AMP FUSIBLE DISCONNECT ON
 SHEET E-16) 'SOLAR PANEL SYSTEM SCHEMATIC'. NOTE #3,
 SHEET E-40 STATES CONTRACTOR SUPPLIED 30 AMP BREAKER.
 CORRELATE THESE ITEMS WITH THE INSTALLATION
 SPECIFICATIONS. 408.4
  
 5} INDICATE HOW THE 300 AMPS FOR "MECHANICAL" LOAD WAS
 CALCULATED. 220 NEC.
  
 6} PER 215.2(A) (1) GENERAL FEEDER CONDUCTORS SHALL
 HAVE AN AMPACITY NOT LESS THAN REQUIRED TO SUPPLY THE
 LOAD AS CALCULATED IN PARTS III, IV, AND V OF ARTICLE
 220. THE MINIMUM FEEDER-CIRCUIT CONDUCTOR SIZE, BEFORE
 THE APPLICATION OF ANY ADJUSTMENT OR CORRECTION
 FACTORS, SHALL HAVE AN ALLOWABLE AMPACITY NOT LESS THAN
 THE NONCONTINUOUS LOAD PLUS 125 PERCENT OF THE
 CONTINUOUS LOAD. NO CONTINUOUS LOADS WERE SHOWN IN THE
 CALCULATIONS (LUMINAIRES).
  
 7} SHEET E-5.0 NOTE #1 UNDER LIGHTING CONTROL RELAY
 PANEL INCORRECTLY REFERENCES SHEET E-23. THE SCHEDULES
 ARE ON E-24.
  
 8} SHEET E6.0 LIGHTING FIXTURE COUNTS AND TYPES ARE NOT
 ALL INCLUDED INPUT DATA REPORT AND WATTAGES GIVEN ON
 SHEET E-17.0 DO NOT CORRELATE WITH THAT REPORT. THIS
 PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE
 13-415.1ABC.1.1 FOR TIME CLOCK REQUIREMENTS AND FOR
 LIGHTING DENSITIES. ALL THAT IS REQUIRED FOR THE
 ELECTRICAL REVIEW IS THE BASIC PRESCRIPTIVE
 REQUIREMENTS. SEE 13-415.2.ABC.1 PERFORMANCE
 CALCULATION PROCEDURES, GENERAL.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED
 INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH
 SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR
 LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE
 DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF
 THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE
 DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE
 SCHEDULE TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.
  
 9} SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING, ALSO NOT
 LISTED IN THE FIXTURE SCHEDULE.
  
 10} ON SHEET E7.0 THE CIRCUIT NUMBERS FOR AHU #2 ARE
 MISSING. 408.4 NEC.
  
 11} THE WATER COOLER CIRCUIT NUMBERS IS MISSING. 408.4
  
 12} NO PANEL DESIGNATION OR CIRCUIT NUMBERS ARE GIVEN
 FOR AHU#3 IN THE ELECTRICAL ROOM, ALSO SEE
 110.26(F)(1)(B) REGARDING THE LOCATION OF THAT UNIT.
  
 13} SHEET E-10.0. & E-11.0 PROVIDE DENSITY CALCULATIONS
 PER 13-415.2.ABC.1.3 EXTERIOR BUILDING LIGHTING POWER.
  
 14} SHEET E-16.0 PROVIDE MANUFACTURERS INSTALLATION
 INSTRUCTIONS AND WIRING DIAGRAM FOR THE SOLAR PANEL
 SYSTEM. ALSO SEE 30 AMP DISCONNECT IN THE MAIN
 ELECTRICAL EQUIPMENT ROOM PRESUMABLY FOR THE SOLAR
 SYSTEM, SEE COMMENT #4.
  
 15} WIND LOAD CALCULATIONS MUST BE SUBMITTED FOR THE F8
 FIXTURE ON SHEET E-16.0 AS NOTE #1 INDICATES, BEFORE IT
 CAN BECOME PART OF THIS PERMIT.1609.1 FBC.
  
 16} THE MAIN ELECTRICAL EQUIPMENT ROOM SHOWN ON SHEET
 E-16.0 SHOWS ONE EXIT DOOR ON THE EAST SIDE OF THE
 ROOM. SHEETS E-2.0 AND E-10.0 SHOW A SECOND DOOR ON THE
 SOUTH SIDE UNDER AHU #3 IS TO BE LOCATED. CORRELATE THE
 SHEETS TO SHOW THE DESIGNERS INTENT. 106.1.1 FBC AS
 AMENDED.
  
 17} SHEET E-16.0 SOLAR PANEL SYSTEM SCHEMATIC.
 REGARDING GROUNDING-690.47(C) (1) A GROUNDING-ELECTRODE
 CONDUCTOR SHALL BE CONNECTED BETWEEN THE IDENTIFIED DC
 GROUNDING POINT TO A SEPARATE DC GROUNDING ELECTRODE.
 THE DC GROUNDING-ELECTRODE CONDUCTOR SHALL BE SIZED
 ACCORDING TO 250.166. THE DC GROUNDING ELECTRODE SHALL
 BE BONDED TO THE AC GROUNDING ELECTRODE TO MAKE A
 GROUNDING ELECTRODE SYSTEM ACCORDING TO 250.52 AND
 250.53. THE BONDING CONDUCTOR SHALL BE NO SMALLER THAN
 THE LARGEST GROUNDING ELECTRODE CONDUCTOR, EITHER AC OR
 DC. INDICATE SIZE AND BONDING TO THE A/C GEC SYSTEM.
  
 SHEET E-18.0
  
 18} THE CIRCUITS FOR AHU #1,2&3 DO NOT CORRELATE WITH
 THE SPECIFICATIONS AND SCHEDULES ON SHEET AC-5. 408.4
 NEC.
  
 19} PANEL "WF" HAS ALL CIRCUITS LISTED AS FEEDING WATER
 FEATURE #6, ONE SHOULD BE DESIGNATED FOR WF #5, SEE
 SHEET E-4.0.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  