Plan Review Notes
Plan Review Notes For Permit 09020043
Permit Number 09020043
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-02-11 13:36:40ALTHOUGH NOT ILLUSTRATED ON THE DRAWINGS, THE FIRE
 ALARM ANNUNCIATOR PANEL WILL BE LOCATED IN THE LOBBY
 NEAR THE FRONT ENTRANCE DOOR PER A CONVERSATION WITH
 MICHAEL CARIGNAN OF DESIGN ELECTRICAL CONSTRUCTION.
  
 PLANS APPROVED AND STAMPED WITH THE FOLLOWING
 REQUIREMENTS:
  
 1) FIRE ALARM SHALL BE UL CERTIFICATED FOR CENTRAL
 STATION SERVICE.
 2) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM.
 3) FIRE ALARM TO BE CLASS A OR FULLY ADDRESSABLE.