| Date |
Text |
| 2009-02-23 11:46:49 | DENIED |
| | REFERENCE: |
| | FBC-2004 FUEL GAS |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. -- PIPING IS DRAWN ON THE FLAT AND IT |
| | CAN NOT BE DETERMINED HOW THE PIPING FROM THE BBQ IS |
| | BEING INSTALLED. -- SHOW THE LENGTH OF ALL PIPE |
| | SECTIONS. |
| | ****NO WRITTEN RESPONSE, COMMENT NOT ADDRESSED. THE |
| | DRAWING IS NOT IN ISOMETRIC FORM. (SEE EXAMPLE OF |
| | ISOMETRIC ATTACHED). AS DRAWN IT IS UNCLEAR IF PIPE |
| | SECTIONS ARE HORIZONTAL OR VERTICAL. PLANS ARE REQUIRED |
| | TO BE IN ISOMETRIC FORM. THE LENGTH OF PIPE PRIOR TO |
| | THE RISER FOR THE BBQ & FIREPLACE IS NOT INDICATED AS |
| | WELL AS THE LAST SECTION OF PIPE TO THE FIREPLACE. |
| | |
| | 2. OK |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****IT IS NOT CLEAR IF THE SECTION OF PIPE AFTER THE |
| | 170 FOOT SECTION IS INSIDE THE HOUSE OR OUTSIDE. NO |
| | LENGHT IS INDICATED. |
| | |
| | ********NEW COMMENT******** |
| | |
| | 1B. A UNION IS REQUIRED DOWNSTREAM OF THE SHUT OFF |
| | VALVES FOR THE REGULATOR TO THE POOL HEATERS AND FOR |
| | THE REGULATOR TO THE LAST BBQ/FIREPLACE. SECTIONS |
| | 406.7.1 & 410.2(4). PLEASE INDICATE ON ISOMETRIC. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |