 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.*** COPIES OF ENGINEERED DRAWINGS CANNOT BE
 SUBMITTED OR REVIEWED.
  
 2} A PERMIT FOR THE HOOD MUST BE APPLIED FOR PRIOR TO
 OR IN CONJUNCTION WITH THE THIS APPLICATION, FOR
 MECHANICAL REVIEW. 106.1 FBC.
  
 3} PLANS FOR THE SUPPRESSION SYSTEM MUST BE SUBMITTED
 FOR FIRE REVIEW. 106.1.1.1 FBC AS AMENDED.
  
 4} THE PLANS SUBMITTED DO NOT CORRELATE WITH THE
 DESCRIPTION ON THE APPLICATION. SUBMIT FLOOR PLANS
 SHOWING THE LOCATION OF THE PANEL AND THE
 EQUIPMENT.106.1.1 FBC.
  
 5} THE #1/0 FEEDERS FROM DISCONNECT "E" (FUSED AT 150
 AMPS) ARE NOT RATED FOR THE 152.5 AMPS GIVEN IN THE
 CALCULATIONS.. 310.16 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  