Plan Review Notes
Plan Review Notes For Permit 09020001
Permit Number 09020001
Review Stop E
Sequence Number 3
Notes
Date Text
2009-12-29 11:51:35 
  
 REVISION DENIED
  
 THE FOLLOWING ARTICLES ARE FROM THE 2005 NEC.
  
 1} 240.24 (E) NOT LOCATED IN BATHROOMS IN DWELLING
 UNITS AND GUEST ROOMS OR GUEST SUITES OF HOTELS AND
 MOTELS, OVERCURRENT DEVICES, OTHER THAN SUPPLEMENTARY
 OVERCURRENT PROTECTION, SHALL NOT BE LOCATED IN
 BATHROOMS.*** REMOVING THE WALL FROM THE DRESSING AREA
 NOW CREATES THIS VIOLATION.
  
 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  