| 2009-02-10 10:29:35 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED, |
| | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 |
| | FS, RESPECTIVELY. |
| | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL |
| | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, |
| | IF EXEMPTIONS APPLY. |
| | |
| | 2} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS |
| | DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES |
| | FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3 |
| | FBC AS AMENDED. |
| | |
| | 3} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN |
| | PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE |
| | EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE PLAN |
| | |
| | 4} NOT ENOUGH INFORMATION TO DETERMINE COMPLIANCE WITH |
| | THE NEC OR OTHER PERTINENT CODES. 106.1.1 FBC |
| | "CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL (SEE ALSO SECTION 106.3.5). |
| | |
| | 5} PLEASE SUBMIT A FLOOR PLAN AND INDICATING THE |
| | LOCATION OF ALL EQUIPMENT AND DEVICES BEING INSTALLED |
| | UNDER THE SCOPE OF THIS APPLICATION.106.1.1 FBC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |