| 2009-02-06 16:43:00 | BUILDING PLAN REVIEW |
| | PERMIT: 09020001 |
| | ADD: 101 NORTH CLEMATIS STREET |
| | CONT: MARCINKO AND RAPPA CONST. INC. |
| | TEL: (561)###-#### |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION |
| | SHALL BE INDICATED ON THE DRAWINGS. |
| | |
| | 4) INDICATE THE USE AND OCCUPANCY OF THE BUILDING PER |
| | FBC CHAPTER 3 AND TABLE 503 AND THE TYPE OF BUILDING |
| | PER CHAPTER 6 AND TABLE 601. |
| | |
| | 5) ADDITIONAL INFORMATION IS REQUIRED TO CLEARLY SHOW |
| | THE EXTENT OF THE WORK. PROVIDE AN EXISTING AND A |
| | PROPOSED FLOOR PLAN SHOWING ALL AFFECTED AREAS. THE |
| | DRAWINGS SUBMITTED SHALL BE OF DRAFTSMAN QUALITY |
| | SHOWING ALL DIMENSIONS OF THE WORK AREA. NOTE: PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. 106.1.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| | THE LOCATION, NATURE & EXTENT OF THE WORK PROPOSED & |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, AND RULES |
| | AND REGULATIONS AS DETERMINED BY THE BUILDING OFFICIAL. |
| | PROVIDE A WALL LEGEND SHOWING THE EXISTING WALLS AND |
| | THE NEW WALLS WITH A DETAIL OF EACH WALL. |
| | |
| | 6) 2004 FBC (EXISTING) 301.5 A DESIGN PROFESSIONAL OR |
| | AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THIS CODE. STATE THE LEVEL OF ALTERATION ON THE PLANS. |
| | |
| | 7) THE SHEETS SUBMITTED SHALL BE SIGN, SEAL AND DATED |
| | PER SECTION 106.1/ FAC 61G15-23.002/ 61G1-16.004 AND |
| | 481.221. |
| | NOTE: A COMPLETE REVIEW CANNOT BE ACCOMPLISHED WITH THE |
| | DRAWINGS SUBMITTED; ADDITIONAL MAY BE MADE WHEN PLANS |
| | WITH SUFFICIENT INFORMATION ARE SUBMITTED. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| | |