| Date |
Text |
| 2009-02-11 16:13:41 | DENIED |
| | REFERENCE: |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 (ADMIN) |
| | |
| | A. APPLICATION STATES "MOVING GAS LINE FOR EXISTING |
| | RESIDENTIAL GAS RANGE BACK 3 FEET. PLANS ALSO SHOW |
| | EXISTING 50,000 BTU GAS GRILL TO BE RECONNECTED TO GAS |
| | LINE BEING MOVED" AS WELL AS "125,000 BTU POOL HEATER |
| | TO BE RECONNECTED". APPLICATION STATES "DESCRIBE |
| | PROJECT IN DETAIL" (FAILURE TO DO SO MAY RESULT IN |
| | DELAYS). -- RESUB SHEET SUBMITTED WITH PLANS INDICATES |
| | THAT THE GAS LINE FOR THE EXISTING GAS GRILL TO BE |
| | ADDED TO RISER DIAGRAM. (NOT PREVIOUSLY REVIEWED). -- |
| | PLEASE INDICATE ALL WORK TO BE DONE ON THE APPLICATION |
| | FOR PERMIT. SECTION 105.1. -- PLEASE INDICATE ON THE |
| | PLANS WHICH WORK IS EXISTING AND WHICH WORK WILL BE |
| | NEW. SECTION 106.1.1 AND TABLE 402.4(2). |
| | |
| | B. SINCE THE SUBMITTAL SHEET INDICATES A GAS LINE TO BE |
| | ADDED FOR THE GAS GRILL, PLEASE SUBMIT THE FOLLOWING |
| | INFORMATION: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. (PREVIOUS PERMITS INDICATE A GAS |
| | GENERATOR). |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). -- (PREVIOUS PERMITS INDICATE A GAS |
| | GENERATOR). |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | 5. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |