| 2009-01-29 07:35:15 | 2004 FBC W/2007 REVISIONS | | | REROOF 3/12 SLOPE AND FLAT | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES AND | | | FASTENING OPTIONS LISTED IN THE GAF MODIFIED ROOF | | | PRODUCT APPROVAL (07-1203.01) WILL BE INSTALLED. CIRCLE | | | THE APPROPRIATE ITEMS ON THE NOA. | | | | | | 2) SUBMIT RAS 117 CALCULATIONS FOR ENHANCED FASTENING | | | FROM AN ENGINEER, ARCHITECT OR REGISTERED ROOF | | | CONSULTANT AS REQUIRED BY LIMITATION NUMBER 7 ON PAGE | | | 30 OF THE GAF MODIFIED ROOF NOA. TWO SIGNED AND SEALED | | | COPIES ARE REQUIRED. | | | | | | 3) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | | BE REQUIRED. FS 713 | | | | | | ROBERT MC DOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|