| 2009-10-09 17:37:22 | |
| | |
| | ** DENIED ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE NOTES FORM PREVIOUS REVIEW. PLANS |
| | STILL INDICATE STANDARD LIGHTING CONTROL DEVICES SUCH |
| | AS SP DIMMERS. PLAN CONTAINS |
| | A NOTE WHICH MENTION TO SEE DETAILS ON SHEET E2.1. |
| | HOWEVER THE DETAIL AND TYPES OF DEVICES DO NOT COMPLY |
| | WITH SECTIONS FOR PRESCRIPTIVE REQUIREMENTS FOR NEW |
| | BEING INSTALLED. |
| | THE NEW TYPES OF SWITCHES ARE DEVICES WHICH GO UP TO |
| | 8HRS. THE CODE DOES NOT ALLOW MORE THAN FOUR. THE CODE |
| | REQUIRES THE OCCUPANT TO SEE ALL LIGHTING WHICH IS |
| | BEING OVER RIDDEN OR MEET EXCEPTIONS. THE DEVICE IS NOT |
| | LOCATED SO THE OCCUPANT CAN SEE LIGHTING BEING |
| | CONTROLLED AND THE OVER RIDE DEVICE SPECIFIED ON PLANS |
| | ( SSA-200) DOES NOT MEET EXCEPTION FOR PILOT/INDICATOR |
| | LIGHTS. |
| | THE DIAGRAM ALSO INDICATES A SQUARE D PRODUCT |
| | #8501C015V20 WHICH DOES NOT COME UP ON THEIR WEBSITE |
| | BUT IS ACTUALLY NOTED AS A MANUAL OVER RIDE OF TIMED |
| | SYSTEM WHICH CAN LEAVE ON DEVICES PERMANENTLY WITHOUT |
| | AUTOMATED CONTROL. AS SHOWN ON DETAIL THE SPDT SWITCH |
| | WILL BYPASS TIMED OVER RIDE ENERGIZING THE COIL ON LCP |
| | AND LEAVE LIGHTS ON INDEFINITELY. THIS DOES NOT MEET |
| | THE INTENT OF ENERGY CODE WHICH WILL TURN OFF LIGHTING |
| | WHEN A BUILDING IS NO OCCUPIED. |
| | |
| | THE LIGHTING CONTROLS FOR EXTERIOR LIGHTS CAN NOT BE |
| | CONFIRMED MEETING 13-415.1.ABC.1.4. THIS SECTION OF THE |
| | CODE REQUIRES ONE OF THE TWO METHODS OR BOTH. NOTE ON |
| | PLANS MENTIONS TO EXISTING CONTROL HOWEVER NO |
| | INFORMATION COULD BE LOCATED. PLEASE VERIFY WHAT IS |
| | EXISTING IF NEW CONTROL IS NOT INSTALLED. |
| | THE CODE REQUIRES THIS TO BE AN ASTRONOMICAL TIME CLOCK |
| | WITH A MINIMUM BACK UP FOR PROGRAMMING. CURRENT CODE |
| | REQUIRES 10HRS BACK UP. WHEN LOCATION WAS ORIGINALLY |
| | BUILT IT WOULD BE UNDER MINIMUM OF THE 2001 FBC IF NOT |
| | INSTALLING NEW CONTROLS. |
| | SEE NEW AREAS OUTSIDE. |
| | PRESCRIPTIVE C NOW SUBMITTED FOR FOR TOTAL AREAS ( NEW |
| | ONLY). CALL AS THIS CAN BE GONE OVER. PREVIOUS METHOD |
| | SUBMITTED WAS B, NOW METHOD IS C. |
| | |
| | 2) NOTE: AS NOTED ON THE PREVIOUS REVIEW. REVIEW FOR |
| | MINIMUM CODE COMPLIANCE FOR LIGHTING PERFORMANCE |
| | CALCULATIONS CAN NOT BE DONE WITHOUT A COMPLETE FIXTURE |
| | LEGEND/SCHEDULE. THE A SHEETS ARE NOT SUBMITTED WIHT |
| | THE ELECTRICAL. THANK YOU FOR THE COPY ON THE BACK OF |
| | THE CALCULATIONS, HOWEVER BASED ON THE FIXTURES LISTED, |
| | NOT ALL FIXTURES WHICH ARE ON PLANS ARE SHOWN/NOTED. |
| | IS THERE ANY INFORMATION ON EIXSTING FIXTURES? |
| | PLEASE SUBMIT A FIXTURE LEGEND/SCHEDULE ON ELECTRICAL |
| | PLANS FOR REVIEW. |
| | 13-415.2.ABC.1.1,.1.2, 13-415.2.ABC.1, 13-415.2.C |
| | |
| | 3) NOTE: TO DATE NO SUB-PERMITS HAVE BEEN APPLIED FOR |
| | ELECTRICAL, PLUMBING, MECHANICAL, FIRE ALARM, OR LOW |
| | VOLTAGE SYSTEMS. |
| | FBC 105.1 |
| | |
| | 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY |
| | NOTICE GIVEN AT THIS TIME DUE TO REPEAT COMMENTS FOR |
| | CODE COMPLIANCE. |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO THE |
| | VALUATION OF THE PROJECT. NO ADJUSTMENT FOR APPLIED |
| | SCOPE OF WORK HAS BEEN SUBMITTED FOR VERIFICATION. |
| | ALL LABOUR, MATERIALS, EQUIPMENT, DESIGN COSTS ETC ARE |
| | REQUIRED TO BE FIGURED EVEN IF OWNER SUPPLIED. FBC |
| | 108.3 |
| | THE ORIGINAL SCOPE OF WORK AND APPLIED VALUE IS |
| | SUBSTANTIALLY LESS THAN THE WORK AT THIS TIME. |
| | |
| | |
| | |
| | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |