Plan Review Notes
Plan Review Notes For Permit 09010434
Permit Number 09010434
Review Stop E
Sequence Number 6
Notes
Date Text
2009-10-09 17:37:22 
  
 ** DENIED **
  
  
 1) NOTE: PLEASE SEE NOTES FORM PREVIOUS REVIEW. PLANS
 STILL INDICATE STANDARD LIGHTING CONTROL DEVICES SUCH
 AS SP DIMMERS. PLAN CONTAINS
 A NOTE WHICH MENTION TO SEE DETAILS ON SHEET E2.1.
 HOWEVER THE DETAIL AND TYPES OF DEVICES DO NOT COMPLY
 WITH SECTIONS FOR PRESCRIPTIVE REQUIREMENTS FOR NEW
 BEING INSTALLED.
 THE NEW TYPES OF SWITCHES ARE DEVICES WHICH GO UP TO
 8HRS. THE CODE DOES NOT ALLOW MORE THAN FOUR. THE CODE
 REQUIRES THE OCCUPANT TO SEE ALL LIGHTING WHICH IS
 BEING OVER RIDDEN OR MEET EXCEPTIONS. THE DEVICE IS NOT
 LOCATED SO THE OCCUPANT CAN SEE LIGHTING BEING
 CONTROLLED AND THE OVER RIDE DEVICE SPECIFIED ON PLANS
 ( SSA-200) DOES NOT MEET EXCEPTION FOR PILOT/INDICATOR
 LIGHTS.
 THE DIAGRAM ALSO INDICATES A SQUARE D PRODUCT
 #8501C015V20 WHICH DOES NOT COME UP ON THEIR WEBSITE
 BUT IS ACTUALLY NOTED AS A MANUAL OVER RIDE OF TIMED
 SYSTEM WHICH CAN LEAVE ON DEVICES PERMANENTLY WITHOUT
 AUTOMATED CONTROL. AS SHOWN ON DETAIL THE SPDT SWITCH
 WILL BYPASS TIMED OVER RIDE ENERGIZING THE COIL ON LCP
 AND LEAVE LIGHTS ON INDEFINITELY. THIS DOES NOT MEET
 THE INTENT OF ENERGY CODE WHICH WILL TURN OFF LIGHTING
 WHEN A BUILDING IS NO OCCUPIED.
  
 THE LIGHTING CONTROLS FOR EXTERIOR LIGHTS CAN NOT BE
 CONFIRMED MEETING 13-415.1.ABC.1.4. THIS SECTION OF THE
 CODE REQUIRES ONE OF THE TWO METHODS OR BOTH. NOTE ON
 PLANS MENTIONS TO EXISTING CONTROL HOWEVER NO
 INFORMATION COULD BE LOCATED. PLEASE VERIFY WHAT IS
 EXISTING IF NEW CONTROL IS NOT INSTALLED.
 THE CODE REQUIRES THIS TO BE AN ASTRONOMICAL TIME CLOCK
 WITH A MINIMUM BACK UP FOR PROGRAMMING. CURRENT CODE
 REQUIRES 10HRS BACK UP. WHEN LOCATION WAS ORIGINALLY
 BUILT IT WOULD BE UNDER MINIMUM OF THE 2001 FBC IF NOT
 INSTALLING NEW CONTROLS.
 SEE NEW AREAS OUTSIDE.
 PRESCRIPTIVE C NOW SUBMITTED FOR FOR TOTAL AREAS ( NEW
 ONLY). CALL AS THIS CAN BE GONE OVER. PREVIOUS METHOD
 SUBMITTED WAS B, NOW METHOD IS C.
  
 2) NOTE: AS NOTED ON THE PREVIOUS REVIEW. REVIEW FOR
 MINIMUM CODE COMPLIANCE FOR LIGHTING PERFORMANCE
 CALCULATIONS CAN NOT BE DONE WITHOUT A COMPLETE FIXTURE
 LEGEND/SCHEDULE. THE A SHEETS ARE NOT SUBMITTED WIHT
 THE ELECTRICAL. THANK YOU FOR THE COPY ON THE BACK OF
 THE CALCULATIONS, HOWEVER BASED ON THE FIXTURES LISTED,
 NOT ALL FIXTURES WHICH ARE ON PLANS ARE SHOWN/NOTED.
 IS THERE ANY INFORMATION ON EIXSTING FIXTURES?
 PLEASE SUBMIT A FIXTURE LEGEND/SCHEDULE ON ELECTRICAL
 PLANS FOR REVIEW.
 13-415.2.ABC.1.1,.1.2, 13-415.2.ABC.1, 13-415.2.C
  
 3) NOTE: TO DATE NO SUB-PERMITS HAVE BEEN APPLIED FOR
 ELECTRICAL, PLUMBING, MECHANICAL, FIRE ALARM, OR LOW
 VOLTAGE SYSTEMS.
 FBC 105.1
  
 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY
 NOTICE GIVEN AT THIS TIME DUE TO REPEAT COMMENTS FOR
 CODE COMPLIANCE.
  
 5) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO THE
 VALUATION OF THE PROJECT. NO ADJUSTMENT FOR APPLIED
 SCOPE OF WORK HAS BEEN SUBMITTED FOR VERIFICATION.
 ALL LABOUR, MATERIALS, EQUIPMENT, DESIGN COSTS ETC ARE
 REQUIRED TO BE FIGURED EVEN IF OWNER SUPPLIED. FBC
 108.3
 THE ORIGINAL SCOPE OF WORK AND APPLIED VALUE IS
 SUBSTANTIALLY LESS THAN THE WORK AT THIS TIME.
  
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717