Plan Review Notes
Plan Review Notes For Permit 09010434
Permit Number 09010434
Review Stop E
Sequence Number 5
Notes
Date Text
2009-09-25 16:49:36 
  
  
 ** DENIED PLANS **
  
 ** PERMIT WAS APPLIED FOR UNDER THE 2004 FBC W/ 2007
 REVISIONS.
  
  
  
 1) NOTE: THE SUBMITTED LIGHTING CALCULATIONS ARE FROM
 FLA COM METHOD B UNDER THE NEW CODE.
 PLEASE KNOW THAT CALCULATIONS SHOULD BE UNDER THE CODE
 IN WHICH THE APPLICATION IS UNDER. IF USING THE NEW
 MORE RESTRICTIVE CODE AS SUBMITTED THE DESIGN WATTAGE
 IS HIGHER THAN THE ALLOWANCE. THE EFFECTIVE IS SHOWN
 LOWER THAN ALLOWANCE HOWEVER PER 13-415.AB.5, DISPLAY,
 DECRETIVE LIGHTING IS NO LONGER EXEMPT, OR ALLOWS ANY
 ADDITIONAL ALLOWANCES.
  
 ** PLEASE SUBMIT COMPLIANCE UNDER THE CODE IN WHICH
 PERMIT WAS MADE.
 ** PLEASE CALL TO GO OVER AS THIS IS A TOPIC WHICH HAS
 BEEN TAKEN UP WITH THE STATE ON THE CODE CHANGES AND
 THE ITEMS NOT BEING CHANGED OR REVISED IN THE FLA COM
 PROGRAM.
  
 ** AS THERE IS NO FIXTURE LEGEND/INFORMATION SUBMITTED
 REVIEW FOR CODE COMPLIANCE CAN NOT FULLY BE DONE.
  
 ** METHOD OF CONTROL ON THE IDR IS NOT ALL GOING TO BE
 *MANUAL ON/ OFF*
  
 2) NOTE: PLEASE SEE 13-415.A.ABC.1.1,.1.2, .1.3 AND
 .1.4.
 PREVIOUS PLANS INDICATED THAT ALL EXISTING LIGHTING
 CONTROLS WERE TO REMAIN. HOWEVER NEW PLANS SHOW
 SUBSTANTIAL AMOUNT OF NEW LIGHTING AND WIRING.
 MUST MEET PRESCRIPTIVE FOR NEW CONTROLS BEING
 INSTALLED.
  
 3) NOTE: NEW EXTERIOR LIGHTING SHALL MEET
 13-415.1.ABC.1.4 FOR CONTROLS. NO INFORMATION ON PLANS.
  
 4) NOTE: PLEASE SEE 13-415.2.ABC.1.1, .1.2 FOR EXTERIOR
 LIGHTING ALLOWANCES.
  
 5) NOTE: PLEASE SEE NOTES FROM PREVIOUS PROVISO FOR
 REQUIRED UPDATING OF LOAD CALCULATIONS. THE PLANS DO
 HAVE REVISIONS HOWEVER PLANS ALSO INDICATE CALCULATIONS
 AND CODE SECTIONS WHICH ARE NO LONGER APPLICABLE. SE3E
 E2.1 WHICH SHOWS NEC 220.35. THIS SECTION WAS FROM THE
 2002 NEC.
 PLEASE UPDATE AND REVISE.
  
 6) NOTE: PLANS CONTAIN SEVERAL NEW FIRE ALARM DEVICES
 HOWEVER PER THE SYMBOL LEGEND NO INFORMATION IS
 PROVIDED FOR DEVICES MEETING FBC 11-4.28.1, .2 AND .3.
 ** PLEASE KNOW THAT EVEN AS SEPARATE FIRE ALARM PERMIT
 WILL BE REQUIRED, THE BASE PLANS SHALL SHOW BASE DESIGN
 REQUIRED FOR FIRE, LIFE SAFETY AND ADA COMPLIANCE.
  
 7) NOTE: THE SCOPE OF WORK HAS SUBSTANTIALLY INCREASED.
 THE APPLIED VALUE NEEDS TO BE ADJUSTED PER FBC 108.3
 THE SCOPE SHALL INCLUDE ALL LABOR, MATERIALS, FIXTURES,
 EQUIPMENT, DESIGN COST ETC EVEN IF ANY OF THESE ITEMS
 ARE OWNER SUPPLIED AND NOT PART EQUIPMENT AND OTHER
 ITEMS SUPPLIED BY THE CONTRACTOR.
  
 ** AS STATED ABOVE THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW FOR CODE COMPLIANCE REVIEW? THERE
 MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN
 NOT BE MADE AT THIS TIME.
  
  
  
  
 ** IMPORTANT**
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  