| 2009-10-08 18:30:08 | BUILDING PLAN REVIEW |
| | PERMIT: 09010434 |
| | ADD: 651 OKKECHOBEE BLVD SUITE 150 |
| | CONT: SHAWMUT DESIGN & CONSTRUCTION |
| | TEL: (561)856-6655 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | OCT. 8/2009 |
| | REVISION# 4 REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE A NEW UPDATED LIFE SAFETY PLAN PER |
| | 106.3.5.1.1(7). |
| | 1A)COMPLIED. |
| | |
| | 1B) COMPLIED. |
| | |
| | 1C) SECOND REQUEST, THE MAIN ENTRY DOOR ON TTHE |
| | ORIGINAL PLANS WAS A PAIR OF DOORS. THE CURRENT |
| | REVISION HAS MOVED THE MAIN ENTRY DOOR AND DOWN SIZED |
| | IT TO A SINGLE 3'-4" DOOR.THE ALLOWABLE OCCUPANT LOAD |
| | THROUGH THE 38" 9CLEAR OPENING) DIVIDE BY .2= 190 |
| | OCCUPANTS. THE UPDATED OCCUPANCY COUNT IS 409. THE DOOR |
| | WIDTH IS SHORT OF THE REQUIRED WIDTHFOR 205 OR 41 |
| | INCHES CLEAR OPENINGA MINIMUM OF 43" DOOR. PLEASE |
| | REVIEW SECTION 1025.2 ASSEMBLY MAIN EXIT. |
| | |
| | 1D) SEECOND REQUEST, A1.1 OPEN AIR DINING PLEASE |
| | INDICATE OPENING# 108E TO BE A REQUIRED 90 MINUTE |
| | OPENING PROTECTIVE AS PER SHEET A4.2 AND TABLE 704.8 |
| | PRODUCT APPROVALS SUBMITTED ARE FOR A 16'-0" ROLLING |
| | STEEL DOOR NOA 08-0805.15. |
| | |
| | 1E)COMPLIED. |
| | |
| | 2) COMPLIED. |
| | |
| | 3) SEMI-COMPLIED. MISSING ROLL DOWN FIRE SHUTTER WITH |
| | LARGE MISILLEIMPACT TESTING. SHEET A1.1 INDICATES NEW |
| | EXTERIOR OPENINGS PLEASE INDICATE COMPLIANCE WITH |
| | 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) |
| | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. |
| | |
| | FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2 |
| | COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE |
| | AS FOLLOWS: |
| | 3A) EXTERIOR FOLDING DOOR SYSTEMS- NO APPROVAL WAS |
| | SUBMITTED |
| | 3B) EXTERIOR GLAZED DOORS W/ SIDE LITES & TRANSOM |
| | (100A)- NO APPROVAL WAS SUBMITTED |
| | 3C)HORIZONTAL MULLIONS- NO APPROVAL WAS SUBMITTED |
| | 3D) ROLL DOWN SHUTTERS SUBMITTAL REVIEWED |
| | 3E) ROLL DOWN FIRE SHUTTER W/ LARGE MISSILE IMPACT |
| | TESTING |
| | 3F) CURTAIN WALL- SUBMITTED -NOT REQUIRED? |
| | |
| | 4) SEECOND REQUEST, 106.3.3 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72 |
| | SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 5)SEECOND REQUEST 50% OF THE OCCUPANT LOAD NEEDS TO BE |
| | ABLE TO COME BACK THROUGH THE MAIN ENTRY PLEASE SEE |
| | COMMENT 1C/ SECTION 1025.2. . DISCREPANCY IN PLANS |
| | PLEASE REVIEW A1.1(FLOOR PLAN), A10.1 DETAIL 2( FRONT |
| | ENTRY INTERIOR ELEVATION) AND A4.1(ELEVATIONS) ON THE |
| | FRONT ELEVATIONS MAIN ENTRY MISSING THE DOUBLE DOORS |
| | PLEASE CORRECT THE DISCREPANCY. WITH THE ELIMINATION OF |
| | THE DOUBLE FRONT ENTRY DOOR PLEASE PROVIDE COMPLIANCE |
| | WITH1024.2. |
| | |
| | 6) COMPLIED. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |