Plan Review Notes
Plan Review Notes For Permit 09010434
Permit Number 09010434
Review Stop E
Sequence Number 4
Notes
Date Text
2009-07-03 17:22:12 
  
 ** PROVISO **
  
 1) NOTE: AS NOTED ON PREVIOUS REVIEW THERE IS AN
 INCREASE ON LOAD ON MORE THAN ONE CIRCUIT. IT IS
 UNDERSTOOD THAT THE OVER ALL LOAD MAY NOT BE AFFECT
 HOWEVER THE SPECIFIC CIRCUIT LOAD FOR #29 AND #30 HAS
 INCREASED. THERE IS NO INDICATION ON THE ACTUAL BRANCH
 CIRCUIT PROVIDED AS EXISTING.
 REVISED CIRCUITING ON PLANS COORDINATING WITH REVISED
 PANEL SCHEDULE(S) WILL BE REQUIRED.
 408.4,220,310.16 ETC
 FBC 106.1.1,106.1.2, 106.5 AS RECORD PLANS SHALL
 INCLUDE AN ACCURATE DEPICTION OF WHAT IS LOCATED
 ON-SITE.
  
 ** THESE NEED TO BE SUBMITTED BEFORE INSPECTIONS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  