| 2009-09-28 18:31:45 | BUILDING PLAN REVIEW |
| | PERMIT: 09010434 |
| | ADD: 651 OKKECHOBEE BLVD SUITE 150 |
| | CONT: SHAWMUT DESIGN & CONSTRUCTION |
| | TEL: (561)856-6655 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVISION# 4 REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE A NEW UPDATED LIFE SAFETY PLAN PER |
| | 106.3.5.1.1(7). |
| | 1A) SHEET A1.0 INDICATES A PRIVATE DINING ROOM# 3 BUT |
| | THE OCCUPANT LOAD IS NOT FIGURED IN ON THE OCCUPANCY |
| | LOADS SHEET T1.1. |
| | |
| | 1B) SHEET A1.0 & A1.1 BOTH INDICATE A SLIDING DOOR |
| | LEAVING ONLY ONE EGRESS DOOR INTO AND EXITING THE |
| | PRIVATE DINING ROOM# 3 PLEASE REVIEW SECTION TABLE |
| | 1014.1 SPACES WITH ONE MEANS OF EGRESS, IF 50 OR MORE |
| | OCUPANTS TWO EGRESS DOORS WILL BE REQUIRED . |
| | |
| | 1C) SHEET A1.1 MAIN ENTRY HAS BEEN SHIFTED TO WHERE AN |
| | EXISTING COLUMN IS WITHIN 2'-0" OF THE DOUBLE DOORS |
| | BLOCKING EGRESS FROM ONE OF THE DOORS, PLEASE REVISE |
| | THE MINIMUM CLEAR WIDTH OF EXIT DOORS FOUND ON THE T1.1 |
| | SHEET TO REFLECT THE ONE DOOR NOT BEING ACTIVE. |
| | |
| | 1D) A1.1 OPEN AIR DINING PLEASE INDICATE OPENING# 108E |
| | TO BE A REQUIRED 90 MINUTE OPENING PROTECTIVE AS PER |
| | SHEET A4.2 AND TABLE 704.8 |
| | |
| | 1E) PLEASE ALSO INDICATE THE LOCATION OF PORTABLE FIRE |
| | EXTINGUISHERS AS PER SECTION 906.1. |
| | |
| | 2) PLANS INDICATE NEW WINDOWS AND DOORS WITHIN THE |
| | EXTERIOR ENVELOPE OF THE BUILDING. PLEASE PROVIDE THE |
| | POSSITIVE AND NEGATIVE PRESSURES FOR THE HIGHRISE AS |
| | PER ASCE 7-05, NEGATIVE PRESSURES ARE TAKEN FROM ROOF |
| | LEVEL, POSITIVE FROM GROUND LEVEL. |
| | |
| | 3) SHEET A1.1 INDICATES NEW EXTERIOR OPENINGS PLEASE |
| | INDICATE COMPLIANCE WITH 1609.1.4 PROTECTION OF |
| | OPENINGS IN WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING |
| | THAT RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET |
| | (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS |
| | AND THE BALANCE OF GLAZED OPENINGS IN THE REST OF THE |
| | BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT |
| | RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT |
| | COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E |
| | 1886 AND ASTM E 1996, OR MIAMI-DADE TAS 201, 202 AND |
| | 203 REFERENCED THEREIN AS FOLLOWS: 1. GLAZED OPENINGS |
| | LOCATED WITHIN 30 FEET (9.1 M) OF GRADE SHALL MEET THE |
| | REQUIREMENTS OF THE LARGE MISSILE TEST. 2. GLAZED |
| | OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) ABOVE GRADE |
| | SHALL MEET THE PROVISIONS OF THE SMALL MISSILE TEST. |
| | |
| | FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2 |
| | COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE |
| | AS FOLLOWS: |
| | 3A) EXTERIOR FOLDING DOOR SYSTEMS |
| | 3B) EXTERIOR GLAZED DOORS W/ SIDE LITES & TRANSOM |
| | (100A) |
| | 3C)HORIZONTAL MULLIONS |
| | 3D) ROLL DOWN SHUTTERS |
| | 3E) ROLL DOWN FIRE SHUTTER W/ LARGE MISSILE IMPACT |
| | TESTING |
| | |
| | 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5) DISCREPANCY IN PLANS PLEASE REVIEW A1.1(FLOOR PLAN), |
| | A10.1 DETAIL 2( FRONT ENTRY INTERIOR ELEVATION) AND |
| | A4.1(ELEVATIONS) ON THE FRONT ELEVATIONS MAIN ENTRY |
| | MISSING THE DOUBLE DOORS PLEASE CORRECT THE |
| | DISCREPANCY. WITH THE ELIMINATION OF THE DOUBLE FRONT |
| | ENTRY DOORPLEASE PROVIDE COMPLIANCE WITH1024.2. |
| | |
| | 6) SHEET A12.1 INDICATES IN THE MAIN DINING ROOM# 1 |
| | (106) AN ACCESSIBLE LOCATION AT A TABLE JUST TO THE |
| | RIGHT OF THE MAIN ENTRY PLEASE REVIEW SECTION |
| | 1024.9.1.1 REQUIRING A CLEARR 44" MEANS OF EGRESS WHEN |
| | SERVING AN OCCUPANT LOAD OF 50 OR MORE. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |