2009-09-28 18:31:45BUILDING PLAN REVIEW
 PERMIT: 09010434
 ADD: 651 OKKECHOBEE BLVD SUITE 150
 CONT: SHAWMUT DESIGN & CONSTRUCTION
 TEL: (561)856-6655
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION# 4 REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE A NEW UPDATED LIFE SAFETY PLAN PER
 106.3.5.1.1(7).
 1A) SHEET A1.0 INDICATES A PRIVATE DINING ROOM# 3 BUT
 THE OCCUPANT LOAD IS NOT FIGURED IN ON THE OCCUPANCY
 LOADS SHEET T1.1.
  
 1B) SHEET A1.0 & A1.1 BOTH INDICATE A SLIDING DOOR
 LEAVING ONLY ONE EGRESS DOOR INTO AND EXITING THE
 PRIVATE DINING ROOM# 3 PLEASE REVIEW SECTION TABLE
 1014.1 SPACES WITH ONE MEANS OF EGRESS, IF 50 OR MORE
 OCUPANTS TWO EGRESS DOORS WILL BE REQUIRED .
  
 1C) SHEET A1.1 MAIN ENTRY HAS BEEN SHIFTED TO WHERE AN
 EXISTING COLUMN IS WITHIN 2'-0" OF THE DOUBLE DOORS
 BLOCKING EGRESS FROM ONE OF THE DOORS, PLEASE REVISE
 THE MINIMUM CLEAR WIDTH OF EXIT DOORS FOUND ON THE T1.1
 SHEET TO REFLECT THE ONE DOOR NOT BEING ACTIVE.
  
 1D) A1.1 OPEN AIR DINING PLEASE INDICATE OPENING# 108E
 TO BE A REQUIRED 90 MINUTE OPENING PROTECTIVE AS PER
 SHEET A4.2 AND TABLE 704.8
  
 1E) PLEASE ALSO INDICATE THE LOCATION OF PORTABLE FIRE
 EXTINGUISHERS AS PER SECTION 906.1.
  
 2) PLANS INDICATE NEW WINDOWS AND DOORS WITHIN THE
 EXTERIOR ENVELOPE OF THE BUILDING. PLEASE PROVIDE THE
 POSSITIVE AND NEGATIVE PRESSURES FOR THE HIGHRISE AS
 PER ASCE 7-05, NEGATIVE PRESSURES ARE TAKEN FROM ROOF
 LEVEL, POSITIVE FROM GROUND LEVEL.
  
 3) SHEET A1.1 INDICATES NEW EXTERIOR OPENINGS PLEASE
 INDICATE COMPLIANCE WITH 1609.1.4 PROTECTION OF
 OPENINGS IN WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING
 THAT RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET
 (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS
 AND THE BALANCE OF GLAZED OPENINGS IN THE REST OF THE
 BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT
 RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT
 COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E
 1886 AND ASTM E 1996, OR MIAMI-DADE TAS 201, 202 AND
 203 REFERENCED THEREIN AS FOLLOWS: 1. GLAZED OPENINGS
 LOCATED WITHIN 30 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST. 2. GLAZED
 OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) ABOVE GRADE
 SHALL MEET THE PROVISIONS OF THE SMALL MISSILE TEST.
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 3A) EXTERIOR FOLDING DOOR SYSTEMS
 3B) EXTERIOR GLAZED DOORS W/ SIDE LITES & TRANSOM
 (100A)
 3C)HORIZONTAL MULLIONS
 3D) ROLL DOWN SHUTTERS
 3E) ROLL DOWN FIRE SHUTTER W/ LARGE MISSILE IMPACT
 TESTING
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) DISCREPANCY IN PLANS PLEASE REVIEW A1.1(FLOOR PLAN),
 A10.1 DETAIL 2( FRONT ENTRY INTERIOR ELEVATION) AND
 A4.1(ELEVATIONS) ON THE FRONT ELEVATIONS MAIN ENTRY
 MISSING THE DOUBLE DOORS PLEASE CORRECT THE
 DISCREPANCY. WITH THE ELIMINATION OF THE DOUBLE FRONT
 ENTRY DOORPLEASE PROVIDE COMPLIANCE WITH1024.2.
  
 6) SHEET A12.1 INDICATES IN THE MAIN DINING ROOM# 1
 (106) AN ACCESSIBLE LOCATION AT A TABLE JUST TO THE
 RIGHT OF THE MAIN ENTRY PLEASE REVIEW SECTION
 1024.9.1.1 REQUIRING A CLEARR 44" MEANS OF EGRESS WHEN
 SERVING AN OCCUPANT LOAD OF 50 OR MORE.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved