| Plan Review Notes For Permit 09010434 |
| Permit Number |
09010434 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2009-07-03 14:05:46 | | | | ** TEMP/DENIED | | | | | | | | | 1) NOTE: CALLED ENGINEER, CONTRACTOR AND PERMIT | | | EXPEDITOR. | | | THE SELECTIVE COORDINATION STUDY HAS SOME CONFLICTS | | | WITH A PORTION DATED APRIL OF 2009 WITH COVER SHEET | | | COMPARED TO THE REPORT OF JUNE 2009. A CALLED WAS | | | PLACED TO ENGINEER HOWEVER OFFICE WAS CLOSED. NEED TO | | | GO OVER AS TITLE DOES LIST SECTION TWO AS NORMAL AND | | | SECTION THREE AS EMERGENCY WHEN IN FACT IT APPEARS EACH | | | SECTION CONTAINS NORMAL AND EMERGENCY. ONE DATED IN | | | 04/09 AND THE OTHER 06/09. IT APPEARS THE 04/09 SHOUDL | | | NTO BE IN THE SUBMITTED DOCUMENTS AS THE TIME CURVES | | | AND OTHER SUPPORTING INFORMATION WAS ALL RUN IN 06/09. | | | | | | 2) NOTE: NEED SECOND SET OF SIGNED, DATED AND SEALED | | | FLA-COM LIGHTING PERFORMANCE CALCULATIONS. FBC 13-103, | | | FS 471.025. SPOKE TO NAT HEALY AS NEW CALCULATIONS WILL | | | BE SENT FED-EX. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|