2009-07-03 14:05:46 
 ** TEMP/DENIED
  
  
 1) NOTE: CALLED ENGINEER, CONTRACTOR AND PERMIT
 EXPEDITOR.
 THE SELECTIVE COORDINATION STUDY HAS SOME CONFLICTS
 WITH A PORTION DATED APRIL OF 2009 WITH COVER SHEET
 COMPARED TO THE REPORT OF JUNE 2009. A CALLED WAS
 PLACED TO ENGINEER HOWEVER OFFICE WAS CLOSED. NEED TO
 GO OVER AS TITLE DOES LIST SECTION TWO AS NORMAL AND
 SECTION THREE AS EMERGENCY WHEN IN FACT IT APPEARS EACH
 SECTION CONTAINS NORMAL AND EMERGENCY. ONE DATED IN
 04/09 AND THE OTHER 06/09. IT APPEARS THE 04/09 SHOUDL
 NTO BE IN THE SUBMITTED DOCUMENTS AS THE TIME CURVES
 AND OTHER SUPPORTING INFORMATION WAS ALL RUN IN 06/09.
  
 2) NOTE: NEED SECOND SET OF SIGNED, DATED AND SEALED
 FLA-COM LIGHTING PERFORMANCE CALCULATIONS. FBC 13-103,
 FS 471.025. SPOKE TO NAT HEALY AS NEW CALCULATIONS WILL
 BE SENT FED-EX.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  