| Date |
Text |
| 2009-05-06 13:00:37 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | CITY WPB MUNICIPAL CODE |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | |
| | 4. SHT RE-1 ITEM 33 GLASS WASHER INDICATES 140 DEGREE |
| | HOT WATER BUT SHOWS NO WATER CONNECTION. PLEASE |
| | CLARIFY. SECTIONS 106.1.2 & 601.1. |
| | ****RESPONSE NOTED, COMMENT NOT ADDRESSED ON SHT RE-1 |
| | TABLE. |
| | |
| | 5. OK |
| | |
| | 6. PLEASE CONTACT THE UTILITY DEPT, INDUSTRIAL |
| | PRETREATMENT, ENVIRONMENTAL COMPLIANCE FOR THE REQUIRED |
| | GREASE INTERCEPTOR. PLEASE CONTACT HOLLY MCGRATH, |
| | LABORATORY SUPERVISOR TO DETERMINE THE SIZING OF THE |
| | INTERCEPTOR AND TO DETERMINE THE PROPER OPERATION OF |
| | THE EXISTING GREASE INTERCEPTOR(S). ARTICLE III, |
| | SECTION 90-124(7). |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 7. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE |
| | FOLLOWING INFORMATION FOR REVIEW: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ****RESPONSE, NOTED, COMMENT NOT ADDRESSED. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | ****RESPONSE NOTED, INFORMATION REQUIRED ON PLANS. |
| | |
| | D. OK |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| | |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT THE BTU LOAD FOR THE RANGE, |
| | (120,000) DOES NOT REFLECT THE BTU LOAD ON SHT RE-2 GAS |
| | APPLIANCE TABLE, (180,000). PLEASE CORRELATE. |
| | |
| | H. N/A |
| | |
| | I. N/A |
| | |
| | J. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | ****RESPONSE NOTED, TO BE SHOWN ON RISER DIAGRAM. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |