| 2009-05-14 08:17:39 | **DENIED REVIEW ** |
| | |
| | |
| | |
| | 1) NOTE: PREVIOUS REVIEW NOTE: PLEASE SEE FBC |
| | 13-415.2,13-415.2.ABC.1.1, .1.2. THE NEW SUBMITTED |
| | ENERGY CALCULATIONS CAN NOT BE VERIFIED AS THE PLANS DO |
| | NOT LIST THE FIXTURE, FIXTURE TYPES, FIXTURES WATTAGES |
| | ETC. |
| | NO COMPLIANCE CAN BE KNOWN BASED ON INFORMATION NOT YET |
| | RECEIVED. IT IS NOT POSSIBLE TO REVIEW THE INPUT DATA |
| | REPORT AND COMPARE TO PLANS FOR FIXTURE COUNTS AND TYPE |
| | FOR COMPLIANCE. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO THE |
| | FIXTURES BEING ADDED WHICH MUST BE LISTED WITH A |
| | NATIONALLY RECOGNIZED TESTING LABORATORY. ( NRTL). |
| | EXAMPLES OF SOME HOWEVER NOT ALL WOULD BE. CSA, MET, |
| | ETL, TUV, TUV AMERICA, UL, ETC. PLEASE SEE THE ADOPTED |
| | LIST PER OSHA. |
| | BASED ON THE PRODUCT DATA SUBMITTED THERE WAS NO |
| | LISTING FROM A NRTL READILY SEEN? |
| | NEC 110.3 |
| | |
| | 3) NOTE: SEVERAL NOTES ON THE PLANS STATE ALL LOCATIONS |
| | NOTED HAVE EQUAL OR LESSER POWER REQUIREMENT THAN |
| | PREVIOUS CONNECTED LOADS. HOWEVER BASED ON THE |
| | EQUIPMENT PLANS SUBMITTED THERE IS NEW EQUIPMENT WHICH |
| | DOES INCREASE LOADS. AN EXAMPLE OF THIS IS THE NEW |
| | ELECTRIC OVEN, TILTING SKILLET ETC. |
| | NEED TO SUBMIT THE EXISTING LOADS WITH THE INCREASED |
| | LOADS AND PANEL SCHEDULE SPECIFIC TO THE NEW EQUIPMENT. |
| | BASED ON THE PLANS IT CAN NOT BE DETERMINED IF THE |
| | EXISTING PANELS AND LOADS ON THE SERVICE EQUIPMENT IS |
| | ADEQUATE. |
| | PLEASE COMPLETE AND SUBMIT. |
| | 240.4,310.16,408.4, 220. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |