Plan Review Notes
Plan Review Notes For Permit 09010434
Permit Number 09010434
Review Stop E
Sequence Number 2
Notes
Date Text
2009-05-14 08:17:39**DENIED REVIEW **
  
  
  
 1) NOTE: PREVIOUS REVIEW NOTE: PLEASE SEE FBC
 13-415.2,13-415.2.ABC.1.1, .1.2. THE NEW SUBMITTED
 ENERGY CALCULATIONS CAN NOT BE VERIFIED AS THE PLANS DO
 NOT LIST THE FIXTURE, FIXTURE TYPES, FIXTURES WATTAGES
 ETC.
 NO COMPLIANCE CAN BE KNOWN BASED ON INFORMATION NOT YET
 RECEIVED. IT IS NOT POSSIBLE TO REVIEW THE INPUT DATA
 REPORT AND COMPARE TO PLANS FOR FIXTURE COUNTS AND TYPE
 FOR COMPLIANCE.
  
 2) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO THE
 FIXTURES BEING ADDED WHICH MUST BE LISTED WITH A
 NATIONALLY RECOGNIZED TESTING LABORATORY. ( NRTL).
 EXAMPLES OF SOME HOWEVER NOT ALL WOULD BE. CSA, MET,
 ETL, TUV, TUV AMERICA, UL, ETC. PLEASE SEE THE ADOPTED
 LIST PER OSHA.
 BASED ON THE PRODUCT DATA SUBMITTED THERE WAS NO
 LISTING FROM A NRTL READILY SEEN?
 NEC 110.3
  
 3) NOTE: SEVERAL NOTES ON THE PLANS STATE ALL LOCATIONS
 NOTED HAVE EQUAL OR LESSER POWER REQUIREMENT THAN
 PREVIOUS CONNECTED LOADS. HOWEVER BASED ON THE
 EQUIPMENT PLANS SUBMITTED THERE IS NEW EQUIPMENT WHICH
 DOES INCREASE LOADS. AN EXAMPLE OF THIS IS THE NEW
 ELECTRIC OVEN, TILTING SKILLET ETC.
 NEED TO SUBMIT THE EXISTING LOADS WITH THE INCREASED
 LOADS AND PANEL SCHEDULE SPECIFIC TO THE NEW EQUIPMENT.
 BASED ON THE PLANS IT CAN NOT BE DETERMINED IF THE
 EXISTING PANELS AND LOADS ON THE SERVICE EQUIPMENT IS
 ADEQUATE.
 PLEASE COMPLETE AND SUBMIT.
 240.4,310.16,408.4, 220.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  