Plan Review Notes
Plan Review Notes For Permit 09010434
Permit Number 09010434
Review Stop P
Sequence Number 1
Notes
Date Text
2009-03-03 12:17:21DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 1. ALL SHEETS SHALL CONTAIN THE CITY PLACE MANAGEMENT
 STAMP AS REVIEWED AND SHALL BE INITIALED BY THE
 REVIEWER. THIS IS A CITY PLACE REQUIREMENT.
  
 2. ALL ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENTS SHALL BE INDICATED IN THE
 TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(6) & FS
 481.2055.
  
 3. SHT T1.1 APPLICABLE CODES SHALL INCLUDE THE 2007
 REVISIONS. SECTION 106.1.1.
  
 4. SHT RE-1 ITEM 33 GLASS WASHER INDICATES 140 DEGREE
 HOT WATER BUT SHOWS NO WATER CONNECTION. PLEASE
 CLARIFY. SECTIONS 106.1.2 & 601.1.
  
 5. PLEASE SUBMIT PLUMBING PLANS FOR THE NEW WORK
 INDICATED ON SHT RE-1 ITEMS 24, 25, 27 & 29. SUBMIT A
 WATER RISER DIAGRAM SHOWING ALL PIPE SIZES, VALVES &
 POINT OF CONNECTION TO THE EXISTING WATER SUPPLY
 MAIN(S). SECTIONS 106.3.5.1.3 & 601.1.
  
 6. PLEASE CONTACT THE UTILITY DEPT, INDUSTRIAL
 PRETREATMENT, ENVIRONMENTAL COMPLIANCE FOR THE REQUIRED
 GREASE INTERCEPTOR. PLEASE CONTACT HOLLY MCGRATH,
 LABORATORY SUPERVISOR TO DETERMINE THE SIZING OF THE
 INTERCEPTOR AND TO DETERMINE THE PROPER OPERATION OF
 THE EXISTING GREASE INTERCEPTOR(S). ARTICLE III,
 SECTION 90-124(7).
  
 7. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION FOR REVIEW:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  