2009-02-24 15:13:10***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE 2007 WHICH INCLUDES NFPA 101, 2006 AND
 NFPA 1, 2006 AS OF DECEMBER 31, 2008. FAC 69A-60.004
 AND FAC 69A-60.003.
  
 2) ALL SHEETS ARE TO BE PROVIDED WITH THE STAMP BY CITY
 PLACE MANAGEMENT OFFICE.
  
 3) SEE OTHER REVIEW COMMENTS REGARDING FAC AND FS
 REQUIREMENTS FOR TITLE BLOCKS.
  
 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 5) IF NOT ALREADY PROVIDED, OCCUPANT LOAD SIGNS SHALL
 BE POSTED. PLEASE CONTACT BUREAU OF FIRE PREVENTION AT
 (561) 804-4724 FOR ASSISTANCE.
  
 6) PLANS INDICATE SUITE #150. ALL APPLICABLE ADDRESS
 NUMBERS ARE TO BE NEAR THE FRONT DOOR AND SHALL MEET
 THE CITY OF WEST PALM BEACH SIZE REQUIREMENTS FOR
 COMMERCIAL BUILDINGS.
  
 7) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILINGS.
  
 8) ALTHOUGH NOT IDENTIFIED AS EXITS, IT WOULD APPEAR
 THAT A TABLE AND CHAIR ARRANGEMENT IS OBSTRUCTING EXIT
 DOORS AT THE SOUTHEAST CORNER OF THE BUILDING.
  
 9) WILL THIS WORK IMACT EXISTING FIRE SPRINKLER AND
 FIRE ALARM SYSTEMS?
  
  