| Plan Review Notes For Permit 09010434 |
| Permit Number |
09010434 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-02-24 15:13:10 | ***DENIED*** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH THE FLORIDA FIRE | | | PREVENTION CODE 2007 WHICH INCLUDES NFPA 101, 2006 AND | | | NFPA 1, 2006 AS OF DECEMBER 31, 2008. FAC 69A-60.004 | | | AND FAC 69A-60.003. | | | | | | 2) ALL SHEETS ARE TO BE PROVIDED WITH THE STAMP BY CITY | | | PLACE MANAGEMENT OFFICE. | | | | | | 3) SEE OTHER REVIEW COMMENTS REGARDING FAC AND FS | | | REQUIREMENTS FOR TITLE BLOCKS. | | | | | | 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 5) IF NOT ALREADY PROVIDED, OCCUPANT LOAD SIGNS SHALL | | | BE POSTED. PLEASE CONTACT BUREAU OF FIRE PREVENTION AT | | | (561) 804-4724 FOR ASSISTANCE. | | | | | | 6) PLANS INDICATE SUITE #150. ALL APPLICABLE ADDRESS | | | NUMBERS ARE TO BE NEAR THE FRONT DOOR AND SHALL MEET | | | THE CITY OF WEST PALM BEACH SIZE REQUIREMENTS FOR | | | COMMERCIAL BUILDINGS. | | | | | | 7) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR | | | WALLS AND CEILINGS. | | | | | | 8) ALTHOUGH NOT IDENTIFIED AS EXITS, IT WOULD APPEAR | | | THAT A TABLE AND CHAIR ARRANGEMENT IS OBSTRUCTING EXIT | | | DOORS AT THE SOUTHEAST CORNER OF THE BUILDING. | | | | | | 9) WILL THIS WORK IMACT EXISTING FIRE SPRINKLER AND | | | FIRE ALARM SYSTEMS? | | | | | | | | | MIKE WENNERGREN, | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|