| 2009-02-12 13:29:34 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: ALL PLANS SHALL CONTAIN CITY PLACE MANAGEMENT |
| | STAMP AS REVIEWED. THIS IS A CITY PLACE REQUIREMENT NOT |
| | A LOCAL CODE, ORDINANCE OR LOCAL ADMINISTRATIVE CODE |
| | REQUIREMENT. |
| | |
| | 2) NOTE: ALL TITLE BLOCKS FOR ALL DESIGN TEAMS ARE |
| | REQUIRED TO MEET FLORIDA ADMINISTRATIVE CODE |
| | 61G1-16.004 AND 61G15-23.002. |
| | FLORIDA STATUTES 481.229 AND 471.023 ALSO APPLY FOR |
| | CERTIFICATE OF AUTHORIZATION NUMBERS WHEN APPLICABLE. |
| | PLEASE SEE THAT SOME INFORMATION IS CURRENTLY MISSING |
| | FROM THE ARCHITECTURAL TITLE BLOCKS. |
| | |
| | 3) NOTE: PLEAS KNOW AS OF DECEMBER 31ST, 2008 THE NEW |
| | ADOPTED FLORIDA FIRE PREVENTION CODE AND LIFE SAFETY |
| | CODE CAN BE FOUND ON THE STATE FIRE MARSHAL WEB SITE. |
| | PLEASE SEE COMMENTS FROM FIRE MARSHAL WITH RESPECT TO |
| | THE CORRECT NFPA-1. THE ADOPTED NFPA-101 IS THE 2006 |
| | EDITION. NOT THE 2003 AS STATED ON PLANS. |
| | |
| | 4) NOTE: PLEASE SUBMIT ELECTRICAL PLANS FOR REMODEL |
| | SCOPE OF WORK INCLUDING ANY NEW LIGHT FIXTURE |
| | LOCATIONS, REPLACEMENT, NEW ETC. |
| | AS THERE ARE SEVERAL NEW ITEMS SHOWN FOR EQUIPMENT, |
| | PLANS SHOWING ELECTRICAL CIRCUITING, RECEPTACLES ETC IS |
| | NEEDED TO SHOW MINIMUM CODE COMPLIANCE. |
| | PLEASE BE SURE TO SEE THE 2005 NEC FOR CIRCUITING, |
| | SIZING, LOADS, LOAD CALCULATIONS, OVER CURRENT |
| | PROTECTION ETC |
| | 408.4,310.16,240.4,240,220 ETC |
| | SPECIFIC SECTIONS OF CODES CAN NOT REALLY BE GIVEN |
| | BASED ON THE FACT NO ELECTRICAL PLANS WERE SUBMITTED. |
| | FBC 106.1.1,106.1.2,106.3.5.1.2,106.5 AS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH. PLANS REQUIRED FOR CLARITY, |
| | ADDITIONAL INFORMATION, SCOPE AND RECORD SETS OF PLANS |
| | FOR SCOPE. |
| | |
| | 5) NOTE: *** IMPORTANT. PLEASE SEE FBC |
| | 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 WITH RESPECT TO |
| | ANY *NEW* LIGHTING CONTROLS BEING INSTALLED. THIS IS |
| | NOT FOR EXISTING TO REMAIN THIS IS FOR NEW ONLY. THE |
| | PLANS STATE FOR EXAMPLE NEW TIME CLOCKS HOWEVER DO NOT |
| | SHOW ANY OF THESE. ARE THEY FOR INSIDE OR OUTSIDE |
| | LIGHTING? |
| | PLEASE BE SURE TO SEE THESE SECTIONS AS NOTED AND CALL |
| | TO GO OVER ANY COMMENTS OR CONCERNS. |
| | |
| | |
| | 6) NOTE: PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1,.1.2 |
| | FOR LIGHTING PERFORMANCE CALCULATIONS. |
| | PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE |
| | CALCULATIONS FOR ALL EXISTING PROPOSED NEW FIXTURES. |
| | THE ADDITIONS OF NEW LIGHTING FIXTURES WITH WATTAGES |
| | ARE NOT PERMITTED UNTIL VERIFICATION OF THE EXISTING |
| | LEVELS CAN BE CONFIRMED. IF THE EXISTING DESIGN EXCEEDS |
| | THE STATED MAXIMUM ALLOWANCES IN THE CURRENT CODE THEN |
| | NEW FIXTURES MAY NOT BE ADDED. |
| | ALL OF THESE NEED TO BE SPECIFIC TO THE NEW AND |
| | EXISTING. |
| | |
| | 7) NOTE: PLEASE PROVIDE MANUFACTURES SPECS/CUT SHEETS |
| | FOR NEW PROPOSED LIGHTING. ALL LIGHTING FIXTURES SHALL |
| | BE LISTED AND BY A NRTL. (NATIONALLY RECOGNIZED TESTING |
| | LABORATORY). |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |