Plan Review Notes
Plan Review Notes For Permit 09010434
Permit Number 09010434
Review Stop E
Sequence Number 1
Notes
Date Text
2009-02-12 13:29:34** DENIED REVIEW **
  
 1) NOTE: ALL PLANS SHALL CONTAIN CITY PLACE MANAGEMENT
 STAMP AS REVIEWED. THIS IS A CITY PLACE REQUIREMENT NOT
 A LOCAL CODE, ORDINANCE OR LOCAL ADMINISTRATIVE CODE
 REQUIREMENT.
  
 2) NOTE: ALL TITLE BLOCKS FOR ALL DESIGN TEAMS ARE
 REQUIRED TO MEET FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND 61G15-23.002.
 FLORIDA STATUTES 481.229 AND 471.023 ALSO APPLY FOR
 CERTIFICATE OF AUTHORIZATION NUMBERS WHEN APPLICABLE.
 PLEASE SEE THAT SOME INFORMATION IS CURRENTLY MISSING
 FROM THE ARCHITECTURAL TITLE BLOCKS.
  
 3) NOTE: PLEAS KNOW AS OF DECEMBER 31ST, 2008 THE NEW
 ADOPTED FLORIDA FIRE PREVENTION CODE AND LIFE SAFETY
 CODE CAN BE FOUND ON THE STATE FIRE MARSHAL WEB SITE.
 PLEASE SEE COMMENTS FROM FIRE MARSHAL WITH RESPECT TO
 THE CORRECT NFPA-1. THE ADOPTED NFPA-101 IS THE 2006
 EDITION. NOT THE 2003 AS STATED ON PLANS.
  
 4) NOTE: PLEASE SUBMIT ELECTRICAL PLANS FOR REMODEL
 SCOPE OF WORK INCLUDING ANY NEW LIGHT FIXTURE
 LOCATIONS, REPLACEMENT, NEW ETC.
 AS THERE ARE SEVERAL NEW ITEMS SHOWN FOR EQUIPMENT,
 PLANS SHOWING ELECTRICAL CIRCUITING, RECEPTACLES ETC IS
 NEEDED TO SHOW MINIMUM CODE COMPLIANCE.
 PLEASE BE SURE TO SEE THE 2005 NEC FOR CIRCUITING,
 SIZING, LOADS, LOAD CALCULATIONS, OVER CURRENT
 PROTECTION ETC
 408.4,310.16,240.4,240,220 ETC
 SPECIFIC SECTIONS OF CODES CAN NOT REALLY BE GIVEN
 BASED ON THE FACT NO ELECTRICAL PLANS WERE SUBMITTED.
 FBC 106.1.1,106.1.2,106.3.5.1.2,106.5 AS ADOPTED BY THE
 CITY OF WEST PALM BEACH. PLANS REQUIRED FOR CLARITY,
 ADDITIONAL INFORMATION, SCOPE AND RECORD SETS OF PLANS
 FOR SCOPE.
  
 5) NOTE: *** IMPORTANT. PLEASE SEE FBC
 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 WITH RESPECT TO
 ANY *NEW* LIGHTING CONTROLS BEING INSTALLED. THIS IS
 NOT FOR EXISTING TO REMAIN THIS IS FOR NEW ONLY. THE
 PLANS STATE FOR EXAMPLE NEW TIME CLOCKS HOWEVER DO NOT
 SHOW ANY OF THESE. ARE THEY FOR INSIDE OR OUTSIDE
 LIGHTING?
 PLEASE BE SURE TO SEE THESE SECTIONS AS NOTED AND CALL
 TO GO OVER ANY COMMENTS OR CONCERNS.
  
  
 6) NOTE: PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1,.1.2
 FOR LIGHTING PERFORMANCE CALCULATIONS.
 PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE
 CALCULATIONS FOR ALL EXISTING PROPOSED NEW FIXTURES.
 THE ADDITIONS OF NEW LIGHTING FIXTURES WITH WATTAGES
 ARE NOT PERMITTED UNTIL VERIFICATION OF THE EXISTING
 LEVELS CAN BE CONFIRMED. IF THE EXISTING DESIGN EXCEEDS
 THE STATED MAXIMUM ALLOWANCES IN THE CURRENT CODE THEN
 NEW FIXTURES MAY NOT BE ADDED.
 ALL OF THESE NEED TO BE SPECIFIC TO THE NEW AND
 EXISTING.
  
 7) NOTE: PLEASE PROVIDE MANUFACTURES SPECS/CUT SHEETS
 FOR NEW PROPOSED LIGHTING. ALL LIGHTING FIXTURES SHALL
 BE LISTED AND BY A NRTL. (NATIONALLY RECOGNIZED TESTING
 LABORATORY).
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717