| Date |
Text |
| 2009-02-11 16:55:38 | BUILDING PLAN REVIEW |
| | PERMIT: 09010434 |
| | ADD: 651 OKEECHOBEE BLVD SUITE 150 |
| | CONT: SHAWMUT WOODWORKING AND SUPPLY INC. |
| | TEL: (617)622-7000 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW1 |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 3) 61G1-16.004 THE TITLE BLOCK SHALL MEET THE |
| | REQUIREMENTS BELOW. |
| | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | |
| | 4) FBC 11-5. THE PLANS NEED TO INDICATE THE ACCESSIBLE |
| | DINING AT THE BAR, LOUNGE AND THE THREE PRIVATE DINNING |
| | AREAS. ACCESSIBLE FIXED TABLES SHALL BE DISTRIBUTED |
| | THROUGHOUT THE SPACE OR FACILITY. NO ACCESSIBLE SPACES |
| | ARE SHOWN IN THE AREAS MENTION ABOVE. SHOW COMPLIANCE. |
| | |
| | 5) THE DRAWING SHALL BE APPROVED BY THE CITY PLACE |
| | OFFICE AND CONTAIN THE STAMP OF APPROVAL FROM THAT |
| | OFFICE WITH THE INITIAL OF THE PERSON STAMPING THE |
| | PLANS. NOTE: EACH SHEET REQUIRES THE CITY PLACE OFFICE |
| | STAMP. |
| | |
| | 6) NOTE: FBC 11-4.32.2 SEATING. IF SEATING SPACES FOR |
| | PEOPLE IN WHEELCHAIRS ARE PROVIDED AT FIXED TABLES OR |
| | COUNTERS, CLEAR FLOOR SPACE COMPLYING WITH SECTION |
| | 11-4.2.4 SHALL BE PROVIDED. SUCH CLEAR FLOOR SPACE |
| | SHALL NOT OVERLAP KNEE SPACE BY MORE THAN 19 INCHES |
| | (SEE FIGURE 45). ALL FIXED SEATING IN PUBLIC FOOD |
| | SERVICE ESTABLISHMENTS, IN ESTABLISHMENTS LICENSED |
| | UNDER THE BEVERAGE LAW FOR CONSUMPTION ON THE PREMISES, |
| | AND IN ALL OTHER FACILITIES GOVERNED BY REFERENCE |
| | SECTION 11-4.1 SHALL BE DESIGNED AND CONSTRUCTED IN |
| | ACCORDANCE WITH THE FOLLOWING REQUIREMENTS: |
| | (1) ALL AISLES ADJACENT TO FIXED SEATING SHALL PROVIDE |
| | CLEAR FLOOR SPACE FOR WHEELCHAIRS. |
| | (2) WHERE THERE ARE OPEN POSITIONS ALONG BOTH SIDES OF |
| | SUCH AISLES, THE AISLES SHALL BE NOT LESS THAN 52 |
| | INCHES (1321 MM) WIDE. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | PHONE (561)805-6726 |
| | FAX (561) 805-6676 |
| | [email protected] |
| | |