2009-02-09 09:00:54DENIED BY BUILDING
  
 1) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED BY THE
 ENGINEER SPECIFIES FASTENER SPACING OF 3" O.C. AT THE
 CORNERS. THE MINIMUM FASTENER SEPARATION ALLOWED BY RAS
 117 SHALL NOT BE LESS THAN 4 IN. O.C. SEE ATTACHED.
 ADDITIONAL ROWS OF FASTENERS WILL BE REQUIRED IN ROOF
 ZONE 3.
  
 2) THE ENGINEER'S COVER LETTER REFERENCES FBC
 RESIDENTIAL SECTION R4402.14. THE CITY OF WEST PALM
 BEACH IS NOT LOCATED IN THE HIGH VELOCITY HURRICANE
 ZONE. THEREFORE, THIS SECTION DOES NOT APPLY. PLEASE
 CORRECT. THE ENHANCED FASTENING IS REQUIRED BY FBC
 R301.2.1 AND ALLOWED BY LIMITATION #7 OF THE TAMKO BUR
 NOA NO. 06-0613.06.
  