 APPLICATION #09010415 ELECTRICAL PLAN REVIEW
 219 DYER ROAD 2/11/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE A PANEL SCHEDULE FOR THE METER/MAIN
 COMBINATION PANEL INCLUDING THE OVERCURRENT PROTECTION
 RATINGS.
  
 2} THIS COMMENT IS IN REGARD TO THE SINGLE GROUND ROD
 ON THE RISER DIAGRAM-SHEET E-1: 250.56 RESISTANCE OF
 ROD, PIPE, AND PLATE ELECTRODES:
 A SINGLE ELECTRODE CONSISTING OF A ROD, PIPE, OR PLATE
 THAT DOES NOT HAVE A RESISTANCE TO GROUND OF 25 OHMS OR
 LESS SHALL BE AUGMENTED BY ONE ADDITIONAL ELECTRODE OF
 ANY OF THE TYPES SPECIFIED BY 250.52(A)(2) THROUGH
 (A)(7). WHERE MULTIPLE ROD, PIPE, OR PLATE ELECTRODES
 ARE INSTALLED TO MEET THE REQUIREMENTS OF THIS SECTION,
 THEY SHALL NOT BE LESS THAN 1.8 M (6 FT) APART.***DUE
 TO SOIL RESISTANCE IN WEST PALM BEACH TWO GROUND RODS
 ARE COMMONLY USED, UNLESS THE CONTRACTOR CAN SHOW THE
 ELECTRICAL INSPECTOR HE/SHE CAN ATTAIN 25 OHMS OF
 RESISTANCE.
  
 3} THE EQUIPMENT GROUND RAN WITH THE FEEDERS TO PANEL
 ???B??? MUST BE A MINIMUM OF #6 CU PER 250.122. SHEET
 E-1 RISER DIAGRAM.
  
 4} THE MICROWAVE AND REFRIGERATOR IN THE KITCHEN, SHEET
 E-2, ARE SHOWN ON CIRCUIT #18 ON THE FLOOR PLAN. THIS
 IS A VIOLATION OF 210.23(A)(1) AND (2),- (1)
 ???CORD-AND-PLUG-CONNECTED EQUIPMENT NOT FASTENED IN
 PLACE THE RATING OF ANY ONE CORD-AND-PLUG-CONNECTED
 UTILIZATION EQUIPMENT NOT FASTENED IN PLACE SHALL NOT
 EXCEED 80 PERCENT OF THE BRANCH-CIRCUIT AMPERE RATING.
 (2) UTILIZATION EQUIPMENT FASTENED IN PLACE THE TOTAL
 RATING OF UTILIZATION EQUIPMENT FASTENED IN PLACE,
 OTHER THAN LUMINAIRES (LIGHTING FIXTURES), SHALL NOT
 EXCEED 50 PERCENT OF THE BRANCH-CIRCUIT AMPERE RATING
 WHERE LIGHTING UNITS, CORD-AND-PLUG-CONNECTED
 UTILIZATION EQUIPMENT NOT FASTENED IN PLACE, OR BOTH,
 ARE ALSO SUPPLIED.???
  
 5} THE MICROWAVE SHOWN ON THE FLOOR PLAN AND LISTED IN
 THE LOAD CALCULATION, IS NOT LISTED ON THE PANEL
 SCHEDULE. SEE COMMENT #4
  
 6} A SMOKE DETECTOR NEEDS TO BE ADDED IN THE 2ND FLOOR
 HALLWAY TO COMPLY WITH R313.1 2.???OUTSIDE EACH
 SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
 BEDROOMS.???
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  