| 2009-02-17 16:36:01 | 2004 FBC W2007 REVISIONS |
| | LEVEL 3 ALTERATIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) ON SHEET SP-1 UNDER DESIGN CRITERIA A CHANGE WAS |
| | MADE BY TAPING A PIECE OF PAPER WITH 2006 NFPA-101 ON |
| | IT TO THE PLANS. THIS TYPE OF CORRECTION IS NOT |
| | ACCEPTABLE FOR SIGNED AND DRAWINGS. FS 481 |
| | |
| | 2) BASED ON THE SCOPE OF WORK FOR THIS PROJECT, IT IS |
| | CONSIDERED A LEVEL 3 ALTERATION. PLEASE SPECIFY THE |
| | LEVEL OF ALTERATION ON THE PLANS. FBC EXISTING BUILDING |
| | SECTION 305 |
| | |
| | 3) ON SHEET D-1 THE FIRST FLOOR DEMO PLAN DOES NOT |
| | INDICATE THAT THE EXISTING FOYER WALLS ARE BEING |
| | REMOVED. SHEET A-1 SPECIFIES NEW EXTERIOR WALLS AT THE |
| | FOYER. PLEASE REVISE. |
| | |
| | 4) ON SHEET A-2 THE INTERIOR WALL AT BEDROOM #2 CLOSET |
| | AND THE HALL IS INCORRECTLY SPECIFIED AS AN (E) - |
| | EXISTING EXTERIOR WALL. PLEASE REVISE. |
| | |
| | 5) ON SHEET A-3 THE NOTES SPECIFY CLOSING UP THE |
| | EXISTING GABLE VENTS ON THE INTERIOR. SHOW THAT |
| | COMPLIANCE WITH THE FOLLOWING WILL BE MAINTAINED. |
| | R806.1 VENTILATION REQUIRED. ENCLOSED ATTICS AND |
| | ENCLOSED RAFTER SPACES FORMED WHERE CEILINGS ARE |
| | APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF RAFTERS SHALL |
| | HAVE CROSS VENTILATION FOR EACH SEPARATE SPACE BY |
| | VENTILATING OPENINGS PROTECTED AGAINST THE ENTRANCE OF |
| | RAIN. VENTILATING OPENINGS SHALL BE PROVIDED WITH |
| | CORROSION-RESISTANT WIRE MESH, WITH 1/8 INCH (3.2 MM) |
| | MINIMUM TO ?? INCH (6.4 MM) MAXIMUM OPENINGS. 806.2 |
| | MINIMUM AREA.THE TOTAL NET FREE VENTILATING AREA SHALL |
| | NOT BE LESS THAN 1 TO 150 OF THE AREA OF THE SPACE |
| | VENTILATED EXCEPT THAT THE TOTAL AREA IS PERMITTED TO |
| | BE REDUCED TO 1 TO 300, PROVIDED AT LEAST 50 PERCENT |
| | AND NOT MORE THAN 80 PERCENT OF THE REQUIRED |
| | VENTILATING AREA IS PROVIDED BY VENTILATORS LOCATED IN |
| | THE UPPER PORTION OF THE SPACE TO BE VENTILATED AT |
| | LEAST 3 FEET (914 MM) ABOVE EAVE OR CORNICE VENTS WITH |
| | THE BALANCE OF THE REQUIRED VENTILATION PROVIDED BY |
| | EAVE OR CORNICE VENTS. AS AN ALTERNATIVE, THE NET FREE |
| | CROSS-VENTILATION AREA MAY BE REDUCED TO 1 TO 300 WHEN |
| | A VAPOR BARRIER HAVING A TRANSMISSION RATE NOT |
| | EXCEEDING 1 PERM (57.4 MG/S ?? M2 ?? PA) IS INSTALLED |
| | ON THE WARM SIDE OF THE CEILING. |
| | |