Plan Review Notes
Plan Review Notes For Permit 09010415
Permit Number 09010415
Review Stop B
Sequence Number 1
Notes
Date Text
2009-02-17 16:36:012004 FBC W2007 REVISIONS
 LEVEL 3 ALTERATIONS
  
 DENIED BY BUILDING
  
 1) ON SHEET SP-1 UNDER DESIGN CRITERIA A CHANGE WAS
 MADE BY TAPING A PIECE OF PAPER WITH 2006 NFPA-101 ON
 IT TO THE PLANS. THIS TYPE OF CORRECTION IS NOT
 ACCEPTABLE FOR SIGNED AND DRAWINGS. FS 481
  
 2) BASED ON THE SCOPE OF WORK FOR THIS PROJECT, IT IS
 CONSIDERED A LEVEL 3 ALTERATION. PLEASE SPECIFY THE
 LEVEL OF ALTERATION ON THE PLANS. FBC EXISTING BUILDING
 SECTION 305
  
 3) ON SHEET D-1 THE FIRST FLOOR DEMO PLAN DOES NOT
 INDICATE THAT THE EXISTING FOYER WALLS ARE BEING
 REMOVED. SHEET A-1 SPECIFIES NEW EXTERIOR WALLS AT THE
 FOYER. PLEASE REVISE.
  
 4) ON SHEET A-2 THE INTERIOR WALL AT BEDROOM #2 CLOSET
 AND THE HALL IS INCORRECTLY SPECIFIED AS AN (E) -
 EXISTING EXTERIOR WALL. PLEASE REVISE.
  
 5) ON SHEET A-3 THE NOTES SPECIFY CLOSING UP THE
 EXISTING GABLE VENTS ON THE INTERIOR. SHOW THAT
 COMPLIANCE WITH THE FOLLOWING WILL BE MAINTAINED.
 R806.1 VENTILATION REQUIRED. ENCLOSED ATTICS AND
 ENCLOSED RAFTER SPACES FORMED WHERE CEILINGS ARE
 APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF RAFTERS SHALL
 HAVE CROSS VENTILATION FOR EACH SEPARATE SPACE BY
 VENTILATING OPENINGS PROTECTED AGAINST THE ENTRANCE OF
 RAIN. VENTILATING OPENINGS SHALL BE PROVIDED WITH
 CORROSION-RESISTANT WIRE MESH, WITH 1/8 INCH (3.2 MM)
 MINIMUM TO ?? INCH (6.4 MM) MAXIMUM OPENINGS. 806.2
 MINIMUM AREA.THE TOTAL NET FREE VENTILATING AREA SHALL
 NOT BE LESS THAN 1 TO 150 OF THE AREA OF THE SPACE
 VENTILATED EXCEPT THAT THE TOTAL AREA IS PERMITTED TO
 BE REDUCED TO 1 TO 300, PROVIDED AT LEAST 50 PERCENT
 AND NOT MORE THAN 80 PERCENT OF THE REQUIRED
 VENTILATING AREA IS PROVIDED BY VENTILATORS LOCATED IN
 THE UPPER PORTION OF THE SPACE TO BE VENTILATED AT
 LEAST 3 FEET (914 MM) ABOVE EAVE OR CORNICE VENTS WITH
 THE BALANCE OF THE REQUIRED VENTILATION PROVIDED BY
 EAVE OR CORNICE VENTS. AS AN ALTERNATIVE, THE NET FREE
 CROSS-VENTILATION AREA MAY BE REDUCED TO 1 TO 300 WHEN
 A VAPOR BARRIER HAVING A TRANSMISSION RATE NOT
 EXCEEDING 1 PERM (57.4 MG/S ?? M2 ?? PA) IS INSTALLED
 ON THE WARM SIDE OF THE CEILING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]