| Plan Review Notes For Permit 09010414 |
| Permit Number |
09010414 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-01-30 11:30:09 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. THE INSTALLATION SCHEDULE STATES THAT THE BUILDING | | | IS 62' HIGH, BUT THE WIND LOAD CHART SUBMITTED STATES | | | THIS BUILDING IS 25'. PLEASE REVISE. THIS APPEARS TO BE | | | A TYPO. | | | | | | 2. THE INSTALLATION SCHEDULE STATES THAT THE SUBSTRATE | | | IS CONCRETE. 3320PSI CONCRETE REQUIRED, SEE SHEET 8 OF | | | THE PRODUCT APPROVAL. THIS HOUSE WAS BUILT WITH A | | | SPECIFICATION OF 3000PSI CONCRETE FOR FLOOR AND | | | COLUMNS. PLEASE PROVIDE EVIDENCE THAT THE CONCRETE | | | SUBSTRATE MEETS THE MINIMUM STRENGTH REQUIREMENT, OR | | | USE THE HOLLOW BLOCK SPECIFICATION, OR A DIFFERENT | | | ANCHOR. | | | |
|