Plan Review Notes For Permit 09010408
Permit Number 09010408
Review Stop E
Sequence Number 2
Notes
Date Text
2009-04-07 12:59:54 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 THESE COMMENTS ARE GENERATED FROM SHEET #4.
 THESE ARE REPEAT COMMENTS THAT WERE NOT RESPONDED TO.
 SUBMIT WRITTEN RESPONSE TO THE COMMENTS MADE IN THIS
 REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC,
 106.3.5.4 FBC AS AMENDED.*** THE "LOAD CALCULATION"
 SUBMITTED WITH SOME WIRE AND BREAKER SIZES IS
 INCOMPLETE. THERE ARE BATH CIRCUITS PER 210.11(C)(3),
 ARC FAULT CIRCUITS PER 210.12 AND DINING ROOM
 RECEPTACLE CIRCUITS PER 210.52(B)(1) MISSING FOR
 EXAMPLE. SEE 408.4 NEC. INDICATE THE RATING OF THE
 EXISTING SERVICE. 215.5 NEC.
  
 3} IF THE PANEL SHOWN ON THE PLAN IS NEW, INDICATE THE
 DISCONNECTING MEANS (PROVIDE A RISER DIAGRAM) PER
 230.70 NEC.
  
 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(C), ONE MUST BE ADDED FOR SPACING REQUIREMENTS
 .NEXT TO THE RANGE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  