2009-04-08 14:49:542004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS
  
 DENIED BY BUILDING
  
 1) CORRECTIONS HAVE BEEN MADE TO SHEET 2 OF THE PLANS
 BY USING WHITE-OUT. THIS IS NOT ALLOWED TO BE DONE TO
 SIGNED AND SEALED DRAWINGS. FS 471 AND FBC 106.1.3*
 CITY AMENDMENTS. SEE PREVIOUS COMMENTS #S 1, 2 AND 3.
  
 2) THE R-VALUE OF THE WALL INSULATION ON SHEET 2 HAS
 BEEN CHANGED TO R-19. THE PLANS SPECIFY 2 X 4 WOOD
 FRAME WALLS, THEREFORE ONLY 3-1/2" INSULATION WITH
 R-11CAN BE CORRECTLY INSTALLED. PLEASE CORRECT PLANS
 AND REVISE ENERGY CALCULATIONS. FBC 11-600. CHANGES TO
 SIGNED AND SEALED DRAWINGS ARE REQUIRED TO BE MADE BY
 THE RESPONSIBLE DESIGN PROFESSIONAL. FS 471.
  
 3) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORM. THE FORM INCORRECTLY SPECIFIES R-19
 INSULATION IN THE 2 X 4 EXTERIOR WALLS ( PER PLANS) AND
 THE PROJECT IS AN EXISTING STRUCTURE. PLEASE COORDINATE
 THE FORM WITH THE PLANS AND MAKE CORRECTIONS. FBC
 11-600. SEE PREVIOUS COMMENT #4.
  
 NOTE: REMOVE THE OLD SHEETS FROM THE PLANS AND REPLACE
 WITH THE NEW ONES. LEAVE THE SHEETS THAT HAVE BEEN
 APPROVED AND STAMPED IN THE PLANS, SO THAT THERE IS TWO
 COMPLETE SETS. THE OLD SHEETS THAT WERE REMOVED CAN BE
 SUBMITTED FOR REFERENCE.
  