| Plan Review Notes For Permit 09010408 |
| Permit Number |
09010408 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-04-08 14:49:54 | 2004 FBC W/2007 REVISIONS | | | LEVEL 2 ALTERATIONS | | | | | | DENIED BY BUILDING | | | | | | 1) CORRECTIONS HAVE BEEN MADE TO SHEET 2 OF THE PLANS | | | BY USING WHITE-OUT. THIS IS NOT ALLOWED TO BE DONE TO | | | SIGNED AND SEALED DRAWINGS. FS 471 AND FBC 106.1.3* | | | CITY AMENDMENTS. SEE PREVIOUS COMMENTS #S 1, 2 AND 3. | | | | | | 2) THE R-VALUE OF THE WALL INSULATION ON SHEET 2 HAS | | | BEEN CHANGED TO R-19. THE PLANS SPECIFY 2 X 4 WOOD | | | FRAME WALLS, THEREFORE ONLY 3-1/2" INSULATION WITH | | | R-11CAN BE CORRECTLY INSTALLED. PLEASE CORRECT PLANS | | | AND REVISE ENERGY CALCULATIONS. FBC 11-600. CHANGES TO | | | SIGNED AND SEALED DRAWINGS ARE REQUIRED TO BE MADE BY | | | THE RESPONSIBLE DESIGN PROFESSIONAL. FS 471. | | | | | | 3) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY | | | CALCULATION FORM. THE FORM INCORRECTLY SPECIFIES R-19 | | | INSULATION IN THE 2 X 4 EXTERIOR WALLS ( PER PLANS) AND | | | THE PROJECT IS AN EXISTING STRUCTURE. PLEASE COORDINATE | | | THE FORM WITH THE PLANS AND MAKE CORRECTIONS. FBC | | | 11-600. SEE PREVIOUS COMMENT #4. | | | | | | NOTE: REMOVE THE OLD SHEETS FROM THE PLANS AND REPLACE | | | WITH THE NEW ONES. LEAVE THE SHEETS THAT HAVE BEEN | | | APPROVED AND STAMPED IN THE PLANS, SO THAT THERE IS TWO | | | COMPLETE SETS. THE OLD SHEETS THAT WERE REMOVED CAN BE | | | SUBMITTED FOR REFERENCE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|