| 2009-02-10 16:41:03 | 2004 FBC W/2007 REVISIONS |
| | LEVEL 2 ALTERATION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) ON SHEET 2 OF THE PLANS THE LEVEL OF ALTERATION IS |
| | INCORRECTLY SPECIFIED AS LEVEL 1. PLEASE CHANGE TO |
| | LEVEL 2. SEE 2004 FBC EXISTING BUILDING SECTION 304. |
| | |
| | 2) UNDER DESIGN PARAMETERS ON SHEET 2 ASCE7-05 IS |
| | INCORRECTLY REFERENCED. THE CORRECT REFERENCE FOR THE |
| | 2004 FBC IS ASCE7-02. PLEASE CORRECT. |
| | |
| | 3) THE BATHROOM WINDOWS ARE REQUIRED TO HAVE SAFETY |
| | GLAZING BY FBC R308.4 WHERE THE BOTTOM EDGE OF THE |
| | GLAZING IS LESS THAN 60 INCHES ABOVE ANY STANDING OR |
| | WALKING SURFACE. SPECIFY SAFETY GLAZING ON PLANS OR |
| | SHOW THAT WINDOWS ARE 60 INCHES ABOVE TUB OR SHOWER |
| | FLOORS. |
| | |
| | 4) THE ENERGY CALCULATION FORM THAT WAS SUBMITTED |
| | CONTAINS SEVERAL ERRORS AND IS NOT SIGNED BY THE |
| | OWNER/AGENT. ENERGY CALCULATIONS ARE NOT REQUIRED TO BE |
| | SUBMITTED WHEN THE RENOVATION COST IS LESS THAN 30 PER |
| | CENT OF THE ASSESSED VALUE OF THE STRUCTURE WHICH |
| | APPLIES TO THIS JOB. HOWEVER, THE COMPONENTS BEING |
| | INSTALLED ARE REQUIRED TO MEET THE PRESCRIPTIVE |
| | REQUIREMENTS OF METHOD C. 13-101.2.3 RENOVATIONS. |
| | RENOVATED BUILDINGS SHALL, WHEN APPLICABLE (SEE SECTION |
| | 202), MEET THE PRESCRIPTIVE REQUIREMENTS CONTAINED IN |
| | METHOD C OF SUBCHAPTER 13-6 FOR RESIDENTIAL |
| | APPLICATIONS OF THE CODE FOR INSULATION, HVAC SYSTEMS, |
| | LIGHTING, WATER HEATING SYSTEMS AND EXTERIOR ENVELOPE |
| | FOR THOSE COMPONENTS BEING RETROFITTED OR REPLACED. |
| | |
| | 5) SPECIFY THE FASTENING OPTION THAT WILL BE USED TO |
| | INSTALL THE STORM PANELS. MARK THE APPROPRIATE ITEM ON |
| | THE TABLE ON SHEET 3 OF NOA NO. 06-1012.05 INSTALLATION |
| | DRAWINGS. |
| | |
| | 6) THE PRODUCT APPROVALS FOR THE STORM PANELS ARE |
| | REQUIRED TO BE APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |