Plan Review Notes
Plan Review Notes For Permit 09010388
Permit Number 09010388
Review Stop B
Sequence Number 3
Notes
Date Text
2009-03-04 15:40:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. ADDRESSED.
  
 2. 1ST REVIEW; SEE ANCHOR CHARTS ON THE ACCORDION
 PRODUCT APPROVAL, SHEET 6, MINIMUM STRENGTH REQUIREMENT
 FOR CONCRETE AND PROVIDE INFORMATION REGARDING THE
 EXISTING SUBSTRATE TO SHOW THAT IT MEETS THE MINIMUM
 REQUIREMENT.
  
 2ND REVIEW; NOT ADDRESSED. PLEASE ADVISE AS TO HOW YOU
 HAVE DETERMINED THAT CONCRETE MEETS THE MINIMUM
 STRENGTH OF 3100PSI. PLEASE NOTE THAT YOU MAY
 ALTERNATIVELY USE CONCRETE BLOCK ANCHOR SPACING.
  
 3RD REVIEW; CONTRACTOR WROTE A RESPONSE THAT ACI318-02
 REQUIES 4500PSI MIN CONCRETE TESTED FOR 5000PSI
 CONCRETE STRENGTH OR CO WOULD NOT HAVE BEEN ISSUED.
 PLEASE NOTE THAT ACI318-02 WAS NOT IN EFFECT AT THE
 TIME THAT THIS STRUCTURE WAS BUILT. SOME STRUCTURES IN
 THIS DEVELOPMENT WERE BUILT WITH A BOND BEAM RATHER
 THAN A TIE BEAM. CONCRETE STRENGTH IS SPECIFIED BY THE
 STRUCTURAL ENGINEER, NOT AN ACI REFERENCE. WITHOUT
 PLANS OR CONCRETE TEST THERE IS NO WAY FOR ME TO
 DETERMINE IF CONCRETE IS THE SUBSTRATE AT THE TOP, OR
 THE CONCRETE STRENGTH AT TOP AND BOTTOM.
  
 CONTRACTOR WROTE A RESPONSE THAT THE 6" ANCHOR SPACING
 PROPOSED EXCEEDS CONCRETE BLOCK REQUIREMENTS. SEE
 OPENING 2, FOR EXAMPLE. C2 IS SPECIFIED AT TOP, C4 AT
 BOTTOM (PLEASE REVISE INSTALLATION SCHEDULE TO CLARIFY
 OPTIONS; THIS SHOULD CORRELATE WITH THE ANCHOR CHARTS).
 C2 REQUIRES 3" FOR BOTH C2 AND C4, BUT CONTRACTOR HAS
 SPECIFIED 6" AND 5". THIS IS AN EXAMPLE; MAY APPLY TO
 OTHER OPENINGS; PLEASE CHECK ALL.
  
 CONTRACTOR'S RESPONSE STATES THAT "UNIT 2 -44.5PSF SPAN
 138" @ 108" 9" @ 157" 3" 6" SHOULD BE ACCEPTABLE".
 PLEASE NOTE - 138" SPAN REQUIRES USE OF THE COLUMN FOR
 SPANS UP TO 13'1", WHAT DO ALL OF THE OTHER NUMBERS
 MEAN? 3" REQUIRED, PLEASE SEE ANCHOR CHART PAGE 7. I
 HAVE HIGHLIGHTED ONE SET.
  
 EITHER PROVIDE A PERMIT NUMBER FOR THIS STRUCTURE OR
 PROVIDED CONCRETE TESTS REFERRED TO IN RESPONSE LETTER
 AS EVIDENCE OF 3100 PSI (TOP AND BOTTOM). NOTE THAT
 MANY RESIDENTIAL SLABS ARE POURED AT 2500PSI.
  
 NEW COMMENT:
  
 3. PLEASE SUBMIT TWO IDENTICAL COLLATED SETS OF PERMIT
 DOCUMENTS FOR PERMIT ISSUANCE. FOR INSTANCE, ONLY ONE
 NEW FLOOR PLAN AND ONE REVISED INSTALLATION SCHEDULE
 WAS SUBMITTED. OLD SHEETS CAN BE REMOVED FROM THE SET
 AND SUBMITTED SEPARATELY FOR REFERENCE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU NEED ASSISTANCE
 WITH THE ABOVE ISSUES.
  
  