| Plan Review Notes For Permit 09010363 |
| Permit Number |
09010363 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-01-27 10:01:50 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. SHEET 14, CONCRETE TO BE MINIMUM F'C = 3KSI. PLEASE | | | PROVIDE EVIDENCE THAT THE CONCRETE MEETS THIS | | | REQUIREMENT, OR A SITE SPECIFIC FROM THE ENGINEER | | | ADDRESSING THIS ISSUE, ESPECIALLY AS A RESIDENTIAL | | | CONCRETE SLAB IS USUALLY 2500PSI. FBC16 | | | | | | 2. OPENINGS 1-7,EDGE DISTANCE OF 3 1/4" SPECIFIED ON | | | INSTALLATION SCHEDULE. SEE SHEET 14, FACTOR MUST BE | | | APPLIED TO ANCHOR SPACING WHEN EDGE DISTANCE IS LESS | | | THAN 3 1/2".FBC1609 | | | | | | 3. SEE OPENING 14. IF THE EDGE DISTANCE AT THE TOP IS 3 | | | 1/2", IT IS NOT CLEAR HOW YOU'VE ARRIVED AT SPAN. | | | PLEASE PROVIDE AN EXPLANATION. FBC1609 | | | | | | |
|