2009-01-27 10:01:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SHEET 14, CONCRETE TO BE MINIMUM F'C = 3KSI. PLEASE
 PROVIDE EVIDENCE THAT THE CONCRETE MEETS THIS
 REQUIREMENT, OR A SITE SPECIFIC FROM THE ENGINEER
 ADDRESSING THIS ISSUE, ESPECIALLY AS A RESIDENTIAL
 CONCRETE SLAB IS USUALLY 2500PSI. FBC16
  
 2. OPENINGS 1-7,EDGE DISTANCE OF 3 1/4" SPECIFIED ON
 INSTALLATION SCHEDULE. SEE SHEET 14, FACTOR MUST BE
 APPLIED TO ANCHOR SPACING WHEN EDGE DISTANCE IS LESS
 THAN 3 1/2".FBC1609
  
 3. SEE OPENING 14. IF THE EDGE DISTANCE AT THE TOP IS 3
 1/2", IT IS NOT CLEAR HOW YOU'VE ARRIVED AT SPAN.
 PLEASE PROVIDE AN EXPLANATION. FBC1609
  
  