| Plan Review Notes For Permit 09010361 |
| Permit Number |
09010361 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-02-26 15:46:05 | | | | | | | | | | APPLICATION #09010361 ELECTRICAL PLAN REVIEW | | | 1525 PALM BEACH LAKES BLVD 1/30/09 | | | WEST PALM BEACH, FL. | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | THESE COMMENTS ARE FROM THE PREVIOUS REVIEW WITH NO | | | CHANGES OR RESPONSE: | | | | | | 1} SHEET E-5 ONE LINE POWER DIAGRAM-NEW WORK DOES NOT | | | INDICATE THE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR | | | CIRCUITS 6, 7, AND 8 FOR THE NEW EQUIPMENT, LABEL | | | SAME.215.5 NEC. | | | | | | 2} AS THE MAIN BONDING JUMPER IS SHOWN IN MSBD (SAME | | | DIAGRAM AS ABOVE) INDICATE HOW THE EQUIPMENT MENTIONED | | | IN COMMENT #1 WILL BE BONDED PER 250.96(A), CONDUIT OR | | | EQUIPMENT GROUNDING CONDUCTOR. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|