Plan Review Notes
Plan Review Notes For Permit 09010361
Permit Number 09010361
Review Stop M
Sequence Number 1
Notes
Date Text
2009-02-03 20:56:35REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PROVIDE DETAIL FOR INSTALLATION AND ATTACHMENT OF ROOF
 CURB AND VENTILATOR. SHOW THESE THINGS DESIGNED AND
 INSTALLED FOR WIND RESISTANCE IN ACCORDANCE WITH FBCM
 301.13.
  
 MECHANICAL PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]