| 2009-10-10 08:38:40 | ** DENIED** |
| | |
| | 1) NOTE: PERMIT APPLICATION FOR CHANGE IN OCCUPANCY HAS |
| | STILL NOT BEEN APPLIED FOR AS REQUIRED PER CHAPTER 3 OF |
| | THE FBC. PLEASE ALSO SEE EXISTING BUILDING CODE CHAPTER |
| | 9 FOR CHANGES IN OCCUPANCY. |
| | |
| | 2) NOTE: PLEASE SEE FBC 108.3 AS THE APPLIED VALUE FOR |
| | THE COMPLETE SCOPE OF WORK SHALL INCLUDE ALL LABOR, |
| | EQUIPMENT, MATERIALS, DESIGN COST EVEN IF ANY OF THESE |
| | ARE OWNER SUPPLIED. |
| | |
| | 3) NOTE: A MINIMUM OF TWO ORIGINAL SIGNED, DATED AND |
| | SEALED SETS OF PLANS ARE REQUIRED. BOTH SETS OF PLANS |
| | SUBMITTED ARE PHOTO-COPIES OF SIGNED AND SEALED PLANS |
| | WHICH ARE NOT PERMITTED. SEE FLORIDA STATUTES 471.025 |
| | AND FLORIDA ADMINISTRATIVE CODE 61G15-23.002. |
| | FBC 106.1,106.1.1,106.1.2, ETC |
| | |
| | 4) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS FOR |
| | MINIMUM CODE COMPLIANCE PER EXISTING BUILDING CODE AND |
| | CHANGES IN OCCUPANCY PER 2007 EXISTING BUILDING CODE |
| | CHAPTER 9. |
| | PLEASE BE SURE TO SEE 2005 NEC AS ELECTRICAL IS ALL |
| | REQUIRED TO MEET CURRENT CODES. |
| | PLEASE INCLUDE ALL ELECTRICAL RECEPTACLES, CIRCUITING, |
| | LIGHTING, LIGHTING CONTROLS, SERVICE, DISCONNECTS, |
| | CONDUCTORS, OVER CURRENT PROTECTION, PANEL SCHEDULE(S) |
| | ETC |
| | 230.2,230.70,230.71,230.72,240.4,310.16,408.4, 230.76,2 |
| | 30.79,215.5,250.50,250.122,250.66,220.14,220.12,220.42, |
| | 220.44,220.60 ETC |
| | THERE ARE TOO MANY CODE SECTIONS TO LIST EVERYONE THAT |
| | APPLY TO THIS SCOPE OF WORK AND THE CHANGE IN |
| | OCCUPANCY. |
| | PLEASE BE SURE TO SEE NFPA-101 FOR MINIMUM LIFE SAFETY |
| | CODE REQUIREMENTS. THE CURRENT EDITION IS THE 2006 |
| | NFPA-101 PER FAC 69A-60.004, 69A-3.012 |
| | PLEASE BE SURE TO SEE FBC CHAPTER 13 FOR ENERGY CODE |
| | COMPLIANCE FOR PRESCRIPTIVE REQUIREMENTS. SEE |
| | 13-415.AB.1.1,.1.2, .1.3 AND .1.4. |
| | |
| | ** AS NO ELECTRICAL PLANS WERE SUBMITTED FOR MINIMUM |
| | CODE COMPLIANCE REVIEW THERE MAY BE NEW COMMENTS ON THE |
| | FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | **IMPORTANT** |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |