| 2009-03-03 16:33:35 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 090100345 |
| | ADD: 724 BUNKER RD |
| | CONT: TROPICAL PLUMBING |
| | TEL: (561)856-6655 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 3) SUBMIT A PROPOSED AND AN EXISTING FLOOR PLAN OF THE |
| | SPACE. THESE DRAWING SHALL SHOW ALL AREAS WHERE WORK |
| | SHALL BE PERFORMED. PROVIDE A WALL LEGEND INDICATING |
| | THE TYPE OF WALL TO BE CONSTRUCTED AND WHICH ONES WILL |
| | BE DEMOED. 2004 FBC 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE & |
| | EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 4) NOTE: THE FLOOR PLANS SUBMITTED DO NOT MATCH WHAT WE |
| | HAVE ON RECORD. THEREFORE, IF WORK WAS CARRIED OUT AT |
| | THIS LOCATION WITHOUT PERMITS A FEE MAY BE APPLIED TO |
| | THIS PERMIT APPLICATION. IF THE OWNER CAN PROVIDE |
| | INFORMATION FROM THIS BUILDING DEPARTMENT REGARDING THE |
| | INTERIOR REMODEL OF THE STRUCTURE, THERE WILL BE NO |
| | FEE. |
| | |
| | 5) FBC 106: THE PLANS SUBMITTED SHALL BE OF DRAFTSMAN |
| | QUALITY AND SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. |
| | SUBMIT TWO COMPLETE SETS OF PLANS PREPARED BY A DESIGN |
| | PROFESSIONAL THAT IS REGISTERED WITH THE STATE OF |
| | FLORIDA. PLANS PREPARED BY A DESIGN PROFESSIONAL SHALL |
| | BEAR THE DESIGNER OFFICIAL SEAL, SIGNATURE AND DATE ON |
| | EACH SHEET. FLORIDA STATUTES 471 AND 481. |
| | |
| | 6) FBC 108.4 ANY PERSON WHO COMMENCES ANY WORK ON A |
| | BUILDING, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR |
| | PLUMBING SYSTEM BEFORE OBTAINING THE BUILDING |
| | OFFICIAL???S APPROVAL OR THE NECESSARY PERMITS SHALL BE |
| | SUBJECT TO A PENALTY OF 300 PERCENT OF THE USUAL PERMIT |
| | FEE IN ADDITION TO THE REQUIRED PERMIT FEES. |
| | |
| | 7) FBC 313: MORE INFORMATION IS REQUIRED TO SHOW THE |
| | TYPE OF DAY-CARE FACILITY AT THIS LOCATION. INDICATE |
| | THE NUMBER OF OCCUPANTS / CLIENTS WHO WILL RECEIVE |
| | CARE, MAINTENANCE AND SUPERVISION BY SOMEONE OTHER THAN |
| | THEIR RELATIVE OR LEGAL GUARDIAN. INDICATE THE OCCUPANT |
| | LOAD PER TABLE 1004, THE PROPOSE USE AND OCCUPANCY PER |
| | CHAPTER 3 AND THE TYPE OF CONSTRUCTION PER TABLE 601 |
| | AND TABLE 503 |
| | |
| | 8) 2004 FBC (EXISTING) 301.5 A DESIGN PROFESSIONAL OR |
| | AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THIS CODE. THIS INFORMATION SHALL BE SHOWN ON THE |
| | PLANS. |
| | |
| | 9) FBC 11-4.3. INDICATE THE ACCESSIBLE ROUTE TO THE |
| | BUILDING, THE ACCESSIBLE ROUTE SHALL. TO THE MAXIMUM |
| | EXTENT FEASIBLE, COINCIDE WITH THE ROUTE FOR THE |
| | GENERAL PUBLIC. THE MAIN ENTRANCE TO THE BUILDING SHOWS |
| | AT LEAST TWO STEPS, WHICH WILL NOT MEET THE ACCESSIBLE |
| | REQUIREMENT; SEE SECTION 11-4.8 FOR RAMP REQUIREMENTS. |
| | IF PARKING SPACES ARE PROVIDED; THE ACCESSIBLE SPACE |
| | SHALL BE LOCATED ON THE SHORTEST SAFELY ACCESSIBLE |
| | ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE |
| | ENTRANCE11-406.2. |
| | |
| | 10) FBC (EXISTING) 812.4.1.1 WHEN A CHANGE OF OCCUPANCY |
| | GROUP IS MADE TO A HIGHER HAZARD CATEGORY (LOWER |
| | NUMBER) AS SHOWN IN TABLE 812.4.1, THE MEANS OF EGRESS |
| | SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER 10 OF THE |
| | FBC. PROVIDE A LIFE SAFETY PLAN SHOWING THE MEANS OF |
| | EGRESS, EXIT ACCESS, EXIT, EXIT DISCHARGE AND THE DOORS |
| | WITH THE DIMENSIONS. |
| | |
| | NOTE: A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, |
| | AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. FOR MORE INFORMATION SEE FBC (EXISTING) |
| | CHAPTER 8. A PLUMBING CONTRACTOR CANNOT DO THE INTERIOR |
| | REMODEL OF THE STRUCTURE. A BUILDING, RESIDENTIAL OR |
| | GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMODEL |
| | OF THE STRUCTURE. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE |
| | APPLICABLE. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | PHONE (561)805-6726 |
| | FAX (561) 805-6676 |
| | [email protected] |
| | |