| Date |
Text |
| 2009-11-19 09:07:05 | REVISION SUBMITTAL CHECKLIST. (ONLY 2 SETS OF |
| | EVERYTHING IS REQUIRED). |
| | |
| | 1- DRESSING ROOM REVISION: OK. |
| | |
| | 2-TRUSS PACKAGE: |
| | A) TRUSS LAYOUT AND TRUSS FT1 SHOW TRUSS BEARING ON A |
| | WOOD LEDGER ON ONE SIDE AND BEARING ON THE WALL ON THE |
| | OTHER SIDE. ROOF FRAMING PLAN ON STRUCTURAL DRAWINGS |
| | SHOW TRUSS BEARING ON WOOD LEDGERS ON BOTH SIDES. |
| | REVISE AS REQUIRED TO MATCH. |
| | |
| | B) NEED ENGINEER'S ORIGINAL SIGNATURE AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTE. |
| | |
| | C) REVISE INFORMATION ON TRUSS COVER PAGE. THIS IS NOT |
| | A SINGLE FAMILY RESIDENCE AND THIS IS NOT BROWARD |
| | COUNTY. REVISE AS REQUIRED. |
| | |
| | 3- PARKING LOT LIGHT POLE CALCULATIONS: NEED TO PROVIDE |
| | 2 COPIES WITH ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS |
| | REQUIRED BY CHAPTER 471 FLORIDA STATUTE. ONLY ONE |
| | ORIGINAL WAS SUBMITTED. |
| | |
| | 4- ROOFING BASE SHEET CALCULATIONS ARE OK. JUST MAKE |
| | SURE THAT THE INSULATION TO BE INSTALLED MEETS THE R |
| | VALUE SPECIFIED ON THE ENERGY CALCULATIONS. |
| | |
| | 5- ASBESTOS REPORT. WAITING FOR ENGINEER'S CURRENT |
| | SEAL. |
| | |
| | 6- ROLL DOWN HURRICANE SHUTTERS: |
| | A) REVISE TYPE OF ANCHOR TO BE USED. TYPE "A" IS FOR |
| | 3000PSI CONCRETE. NEED TO USE TYPE "B" TAPCON FOR CMU |
| | CONSTRUCTION. REVISE INSTALLATION SCHEDULE USING TYPE |
| | "B" TAPCON TABLE FROM SHUTTERS DRAWINGS SUBMITTED (SEE |
| | SHEET 4 OF 7). |
| | |
| | 7- ACCORDION SHUTTERS: OK. |
| | |
| | 8- INSWING SINGLE DOOR PRODUCT APPROVAL: OK. |
| | |
| | 9- OWES $130 FOR REVISION FEES. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |
| | |