| Date |
Text |
| 2009-04-14 19:10:01 | ** DENIED/** |
| | |
| | |
| | |
| | 1) NOTE: THE SUBMITTED ENERGY CALCULATIONS DO NOT |
| | COMPLY WITH THE FOLLOWING. THE FBC 13-103.1, FS |
| | 471.025, FAC 61G15-23.002 |
| | BOTH COPIES IN SETS OF DOCUMENTS SUBMITTED DO NOT MEET |
| | MINIMUM SECTIONS ABOVE. ONE COPY SUBMITTED IS IN FACT A |
| | COLORED PHOTO-COPY OF SIGNED DOCUMENTS. IN EITHER CASE |
| | BOTH SUBMITTED ARE NOT SEALED AS REQUIRED. |
| | THE CALCULATIONS CERTIFICATION SHEET CONTAINS THE |
| | STRUCTURAL ENGINEER AS THE PERSON WHOM THE CALCULATIONS |
| | ARE PREPARED BY ALONG WITH A PRINTED NAME AND SIGNATURE |
| | YET NO RAISED SEAL IS PRESENT. PLEASE CONFIRM THE |
| | CALCULATIONS ARE DONE BY MR. GORDON BUCK. THE |
| | CALCULATIONS ALSO CONTAIN THE PRINTED NAME AND |
| | SIGNATURE FROM MR. MARIO FERNANDEZ WHO IS SHOWN AS THE |
| | MECHANICAL AND ELECTRICAL ENGINEER. |
| | |
| | 2) NOTE: LIGHTING ON THE INPUT DATA REPORT STILL NEEDS |
| | TO COORDINATE WITH THE SUBMITTED PLANS. PLEASE TAKE A |
| | LOOK AT EXTERIOR FIXTURES ON PLANS. BY THE SYMBOL |
| | LEGEND ALL OF THESE ARE SHOWN AS RECESSED FLUORESCENT |
| | DOWN LIGHTS. HOW IS THIS POSSIBLE ON THE EXTERIOR |
| | WALLS? |
| | PLEASE SEE THE IDR AS NONE OF THE SITE PARKING LOT |
| | LIGHTS WHICH ARE NOW ON PLANS FOR THE FIRST TIME ARE |
| | INCLUDED. HOW IS THIS POSSIBLE? |
| | PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND SECTION .1.3 FOR |
| | EXTERIOR LIGHTING. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |